Electrical Motor Control Principles
Chapter 7: Perform auto transformer starter control circuits
📚 4 Topics
⚑ What you will be able to do

By the end of this chapter, you will be able to:

  • Apply the principles and methods of autotransformer reduced-voltage starter circuits for three-phase asynchronous motors based on starter control job needs.
  • Correctly connect autotransformer reduced-voltage starter circuits following the proper procedures.
  • Safely debug autotransformer reduced-voltage starter circuits to ensure they work as intended.
  • Accurately diagnose issues in autotransformer reduced-voltage starter circuits using job requirements and manufacturer specifications.
  • Prepare a clear and professional diagnosis report following workplace procedures.

Mastering these skills will help you confidently handle motor control systems, making you a valuable asset in electrical motor control work.

Auto transformer reduced-voltage starters are essential in controlling the starting current and torque of three-phase asynchronous motors, a common component in many Kenyan industries including hospitals, manufacturing plants, and agricultural processing facilities. These starters help protect electrical equipment from excessive electrical and mechanical stress during motor startup, extending the lifespan of the motor and enhancing operational safety. Understanding the principles and methods of autotransformer starter circuits enables technicians and engineers to implement effective motor control solutions that improve energy efficiency and reduce operational costs across diverse sectors such as county government offices, universities, and retail businesses.

7.1.1 Basic Principles of Autotransformer Reduced-Voltage Starters for Three-Phase Asynchronous Motors

Autotransformer reduced-voltage starters operate by initially applying a lower voltage to the motor terminals during startup, which limits the inrush current and reduces mechanical stress on the motor shaft. The autotransformer used in the starter has taps that provide a fraction of the line voltage to the motor, typically 50%, 65%, or 80%, depending on the design and application needs. This reduced voltage decreases the starting current to a safer level, usually around 60-70% of the full voltage starting current, which is vital in environments like university workshops where electrical supply stability is critical.

The motor initially runs at reduced voltage, and once it reaches a predetermined speed, the starter switches the motor to full line voltage for normal operation. This switching is typically done via contactors controlled by an electromechanical or programmable logic controller (PLC) system. The transition must be smooth to avoid sudden torque shocks which could damage mechanical components or cause system instability in facilities such as county referral hospitals where motor-driven equipment must operate reliably.

Example: At a large agricultural cooperative, the autotransformer starter reduces voltage during the start of grain milling motors, thereby preventing voltage dips that could affect other sensitive equipment on the same supply network.

Key Principles of Autotransformer Starting

  • Voltage Reduction: The autotransformer provides a fraction of the full voltage to reduce starting current and torque, preventing electrical and mechanical stress.
  • Current Limiting: Reduced voltage directly limits the starting current, protecting the supply network and motor windings from excessive current draw.
  • Smooth Transition: Switching from reduced voltage to full voltage must be seamless to avoid mechanical shocks and electrical transients.
  • Energy Efficiency: By limiting inrush current, the starter reduces energy losses and voltage drops in the supply system.
  • Motor Protection: The method extends motor life by reducing thermal and mechanical fatigue during startup.

7.1.2 Construction and Components of Autotransformer Starter Circuits

The autotransformer starter circuit consists of several key components arranged to achieve reduced voltage starting and smooth transition to full voltage. The main parts include the autotransformer, line contactor, autotransformer contactor, and bypass contactor, along with protective devices such as overload relays and control circuitry.

The autotransformer itself is a specially designed transformer with a single winding tapped at various points to provide reduced voltage outputs. The line contactor connects the motor directly to the supply for full voltage operation. The autotransformer contactor connects the motor to the autotransformer taps during starting. The bypass contactor connects the motor directly to the line after the motor reaches rated speed, bypassing the autotransformer to avoid unnecessary losses.

Protective devices like thermal overload relays are integrated to monitor motor current and prevent damage from overheating. Control circuits, often using timers or PLCs, manage the sequence of contactor operations to ensure correct timing and safe switching.

Example: At a county government water treatment plant, the control panel for pumping motors integrates an autotransformer starter with overload protection to ensure reliable operation during variable demand periods.

Main Components of Autotransformer Starter Circuits

  • Autotransformer: Provides reduced voltage taps to lower motor voltage during startup.
  • Line Contactor: Switches motor directly to full line voltage after startup.
  • Autotransformer Contactor: Connects motor to reduced voltage taps during starting.
  • Bypass Contactor: Bypasses the autotransformer once motor reaches rated speed.
  • Overload Relay: Protects motor from excessive current and overheating.
  • Control Circuit: Coordinates contactor operation, often with timers or PLCs.

7.1.3 Methods of Starting and Transition in Autotransformer Starter Circuits

The starting method involves energizing the autotransformer contactor and line contactor to supply reduced voltage to the motor. The motor accelerates under this reduced voltage until it attains a speed close to its rated speed. A timer or sensing relay then initiates the transition to full voltage by de-energizing the autotransformer contactor and energizing the bypass contactor, which connects the motor directly to the supply.

Timing is critical in this method to avoid excessive voltage dips or mechanical shocks. The transition usually occurs after a preset time delay that corresponds to the motor reaching approximately 80-90% of its rated speed. In some advanced systems, speed sensors or current sensors provide feedback to optimize the timing precisely.

Example: A retail business with refrigeration compressors uses an autotransformer starter with a PLC-controlled timer to ensure smooth motor starting and prevent voltage dips that affect the store’s lighting and point-of-sale systems.

Steps in Autotransformer Starting and Transition

  1. Initial Energizing: The autotransformer and line contactors close to apply reduced voltage to the motor.
  2. Motor Acceleration: The motor accelerates under reduced voltage, limiting starting current.
  3. Timing Delay: A timer or sensor monitors motor speed or current to determine when to switch.
  4. Transition Initiation: The autotransformer contactor opens, interrupting the reduced voltage supply.
  5. Bypass Contactor Closure: The bypass contactor closes, connecting the motor directly to full line voltage.
  6. Normal Operation: The motor runs at full voltage and speed with overload protection active.

7.1.4 Advantages and Practical Considerations of Using Autotransformer Starters

Autotransformer starters provide significant benefits in industrial and commercial settings where large three-phase motors are used. They reduce the starting current and mechanical stress, improving motor longevity and operational reliability. Additionally, they help maintain voltage stability in the supply network, which is crucial in environments such as hospitals and universities where sensitive electronic equipment operates alongside motor loads.

However, autotransformer starters have practical considerations, including space requirements for the transformer, the initial cost of the equipment, and the need for proper maintenance to ensure reliable operation. The transformer can generate heat and requires adequate ventilation. Furthermore, correct sizing of the autotransformer taps is critical to match the motor starting characteristics and the application's load profile.

Example: A university workshop uses an autotransformer starter for large lathes and milling machines to prevent voltage drops that could disrupt other equipment, demonstrating the importance of selecting appropriate transformer taps and maintaining the equipment regularly.

Advantages of Autotransformer Starters

  • Reduced Starting Current: Limits inrush current to prevent supply voltage dips.
  • Lower Mechanical Stress: Protects motor shaft and driven machinery from sudden torque.
  • Improved Voltage Stability: Minimizes disturbances to other equipment on the same network.
  • Energy Savings: Limits losses associated with high starting currents.
  • Enhanced Motor Life: Reduces thermal and mechanical wear during startup.

Practical Considerations

  • Space and Cooling Requirements: Autotransformers need adequate space and ventilation.
  • Initial Cost: Higher upfront investment compared to direct-on-line starters.
  • Maintenance Needs: Regular inspection and cleaning to prevent overheating and contactor failure.
  • Correct Tap Selection: Essential to balance starting torque and current reduction.
  • Control System Complexity: Requires precise timing or sensor-based control for smooth transitions.

Practice Questions

  1. Explain how an autotransformer starter reduces the starting current of a three-phase asynchronous motor. (6 marks)

  2. Identify and describe five main components of an autotransformer starter circuit and their functions. (10 marks)

  3. Outline the sequence of operations involved in starting and transitioning a motor using an autotransformer starter. (12 marks)

  4. Discuss five advantages and three practical considerations when using autotransformer starters in industrial motor control. (15 marks)

7.2 Connection and Debugging Methods of Autotransformer Reduced-Voltage Starter Circuits of Three-Phase Asynchronous Motor

In many Kenyan industries, including county hospitals, universities, and retail businesses, three-phase asynchronous motors are widely used to drive heavy machinery and equipment. The autotransformer reduced-voltage starter is a common method to limit the starting current and torque, protecting both the motor and electrical network from stress. Understanding how to properly connect and debug these starter circuits is essential for technicians and engineers to ensure reliable and safe motor operation in diverse professional settings.

7.2.1 Connection Principles of Autotransformer Reduced-Voltage Starter Circuits

Correct connection of the autotransformer reduced-voltage starter circuit is crucial to achieve the desired reduction in starting current and prevent damage to motor windings or the power supply system. The autotransformer is connected in series with the motor during startup to provide a reduced voltage, then bypassed upon reaching nominal speed.

Key Elements in Connection

  • Three-Phase Power Supply Integration: The starter circuit must connect properly to the three-phase supply lines ensuring correct phase sequence to avoid motor reversal, which is vital in hospital ventilation systems where motor direction affects airflow.

  • Autotransformer Taps Selection: The autotransformer provides multiple taps (usually 50%, 65%, and 80% of line voltage). Selecting the appropriate tap depends on the motor load characteristics; for example, a bakery using mixers may opt for 65% voltage to balance torque and current.

  • Contactor Arrangement: The circuit uses three contactors: one to connect the autotransformer to the supply during starting, one to bypass the autotransformer after starting, and one for motor connection. Proper interlocking between these contactors prevents simultaneous engagement, avoiding short circuits.

  • Overload Protection Integration: Overload relays must be connected in series with the motor to monitor current and protect against overheating, especially in water pumping stations where prolonged motor operation is common.

  • Control Circuit Wiring: The control wiring includes start and stop push buttons, auxiliary contacts for interlocking, and timers if used. Proper wiring ensures safe operation and prevents unintended starts or stops in commercial buildings.

7.2.2 Step-by-Step Procedure for Connecting the Autotransformer Starter Circuit

Connecting the autotransformer starter circuit requires methodical steps to ensure safety and functionality. The procedure below is applicable in settings such as county government offices where motor-driven ventilation or pumping systems are installed.

  1. Disconnect Power Supply: Ensure the main power supply to the motor circuit is isolated and locked out to prevent accidental energization during wiring.

  2. Mount Starter Components: Secure the autotransformer, contactors, and overload relay on the control panel or mounting board, positioning for easy access and clear wiring paths.

  3. Connect Incoming Power Lines: Wire the three-phase supply lines to the input terminals of the autotransformer and main contactor, verifying correct phase order to prevent motor rotation errors.

  4. Wire the Autotransformer Outputs: Connect the autotransformer secondary taps to the motor terminals via the autotransformer contactor, ensuring firm and insulated connections.

  5. Install Motor Connection: Wire the motor terminals to the output side of the starter circuit, passing through the bypass contactor to allow full voltage application after starting.

  6. Complete Control Circuit Wiring: Connect the start/stop push buttons, auxiliary contacts, overload relay, and any timers according to the wiring diagram, confirming all control devices are rated for the control voltage used.

  7. Check Wiring Against Diagram: Verify all connections match the approved wiring schematic to prevent faults during energization.

  8. Restore Power and Test: Re-energize the supply and test the starter operation by starting and stopping the motor, observing contactor operation and motor response.

7.2.3 Common Faults and Debugging Techniques in Autotransformer Starter Circuits

Debugging autotransformer starter circuits is a critical skill for maintenance personnel in agricultural cooperatives or retail warehouses where motor downtime affects productivity. Faults in these circuits often arise from wiring errors, component failures, or control circuit malfunctions.

Typical Faults and Diagnostic Approaches

  • Motor Does Not Start: Check if the start push button and control circuit are functioning; measure control voltage and verify contactor coil energization. For instance, in a county hospital, a non-starting motor may delay essential services like water pumping.

  • Autotransformer Contactors Fail to Engage: Inspect coil continuity and control wiring; a faulty coil or blown fuse may cause this. Use a multimeter to test coil resistance and verify control circuit integrity.

  • Simultaneous Engagement of Contactors: This can cause short circuits; verify auxiliary contacts and interlocks are correctly wired to prevent contactor overlap.

  • Excessive Starting Current: Indicates autotransformer taps are connected incorrectly or contactor bypass is premature. Measure line voltage during startup and compare with expected reduced voltage values.

  • Overload Relay Trips Frequently: Could be due to motor overload or incorrect setting of the relay. Check motor load conditions and adjust relay settings to manufacturer's specifications.

7.2.4 Testing and Verification Procedures for Autotransformer Starter Circuits

Testing the autotransformer starter circuit after installation or repair ensures safe and efficient operation, which is particularly important in dynamic environments like university laboratories where motor-driven equipment is critical.

  1. Visual Inspection: Examine all wiring connections for looseness, insulation damage, or incorrect termination.

  2. Continuity Tests: Use an ohmmeter to verify continuity of control circuit wiring and contactor coils.

  3. Insulation Resistance Measurement: Test motor windings and autotransformer insulation resistance with a megohmmeter to detect potential insulation breakdown.

  4. Operational Test: Energize the circuit and observe the sequence of contactor engagement and motor starting behavior. Confirm that the autotransformer contactor energizes first, then the bypass contactor.

  5. Voltage Measurement: Measure voltage across motor terminals during startup to verify reduced voltage application; values should match the selected autotransformer tap.

  6. Overload Relay Function Test: Simulate overload conditions to confirm proper tripping of the relay and safe motor shutdown.

  7. Motor Performance Check: Monitor motor current, speed, and temperature during start and run phases to ensure parameters are within specified limits.

Practice Questions

  1. Explain the role of each contactor in an autotransformer reduced-voltage starter circuit and the consequences of incorrect contactor sequencing. (10 marks)
  2. Describe the step-by-step procedure for connecting an autotransformer starter circuit for a three-phase asynchronous motor. (12 marks)
  3. Identify and explain five common faults encountered in autotransformer starter circuits and how to troubleshoot them. (15 marks)
  4. Outline the testing procedures to verify the correct operation of an autotransformer reduced-voltage starter circuit after installation. (13 marks)
The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒7.3 Diagnosis of autotransformer reduced-voltage starter circuits of three-phase asynchronous motor

In Kenyan industries such as hospitals, universities, and county government offices, three-phase asynchronous motors are widely used to drive pumps, compressors, and ventilation systems. Autotransformer reduced-voltage starters are preferred for these motors t…

🔒7.4 Writing Diagnosis Reports

In the Kenyan professional environment, especially in sectors such as healthcare, education, finance, and county administration, clear and accurate diagnosis reports are vital for effective decision-making. Electrical motor control systems, including auto tran…

Chapter Summary

This chapter explored the principles and methods of autotransformer reduced-voltage starter circuits used for three-phase asynchronous motors, highlighting how these circuits reduce starting current and protect motor windings during startup. It detailed the proper connection and debugging techniques necessary to ensure the starter circuits function correctly and safely, emphasizing careful wiring and systematic testing procedures. The chapter also covered diagnostic approaches to identify common faults and operational issues within autotransformer starter circuits, enabling timely maintenance and repair. Furthermore, it outlined the process of writing clear and comprehensive diagnosis reports, which document findings, recommend corrective actions, and support effective communication among technical teams. Together, these topics provide a thorough understanding of both the theoretical and practical aspects of autotransformer starter control circuits in electrical motor applications.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. What is the main purpose of using an autotransformer starter in a three-phase asynchronous motor? (2 marks)
  2. Identify two common methods of connecting an autotransformer reduced-voltage starter circuit. (3 marks)
🔒20 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Explain the principle of autotransformer reduced-voltage starting for a three-phase asynchronous motor and why it is preferred in industrial applications such as in a county hospital's laundry facility. (4 marks)
  2. Describe the typical connection method of an autotransformer starter circuit for a three-phase motor used in a hotel’s cold storage room. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Identify and Explain Autotransformer Starter Components

Refrigeration And Air Conditioning · Level 6
Electrical Motor Control Principles
PRACTICAL ASSESSMENT
TIME: 3 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Identify and explain the main components of an autotransformer reduced-voltage starter circuit including the autotransformer, main and auxiliary contactors, overload relay and control devices as per the provided starter kit.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Digital MultimeterAutotransformer Starter Kit
Insulated Screwdriver SetService Manual for Autotransformer Starter
Pliers
Wire Strippers and Cutters
Insulation Tester (Megger)
Clamp Meter
Electrical Tape
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Autotransformer Starter Kit (includes autotransformer, contactors, overload relay)1 Set per Candidate
2Digital Multimeter1 Pc per Candidate
3Insulated Screwdriver Set1 Set per Candidate
4Pliers1 Pc per Candidate
5Wire Strippers and Cutters1 Pc per Candidate
6Insulation Tester (Megger)1 Pc per Candidate
7Clamp Meter1 Pc per Candidate
8Electrical Tape1 Roll per Candidate
9Service Manual for Autotransformer Starter1 Pc per Station
10Safety Gloves1 Pair per Candidate
11Safety Boots1 Pair per Candidate
12Dust Coat/Overall1 Pc per Candidate
13Safety Goggles1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Identification and Explanation of Components
Wore appropriate PPE (Safety gloves, boots, goggles, dust coat) as per SOPs
(Award 1 mark for correct PPE use, else zero)
1
Handled tools and equipment correctly and safely as per workshop procedure
(Award 1 mark for correct and safe tool handling)
1
Identified the autotransformer and explained its function in the starter circuit
(Award up to 3 marks for correct identification and clear explanation)
3
Identified main and auxiliary contactors and explained their roles
(Award up to 3 marks for correct identification and explanation)
3
Identified overload relay and explained its protective function
(Award up to 3 marks for correct identification and explanation)
3
Identified control devices (push buttons, timers if any) and explained their function
(Award up to 2 marks for correct identification and explanation)
2
Used measuring instruments (multimeter, clamp meter, insulation tester) to verify component specifications
(Award up to 2 marks for correct use and interpretation)
2
Referred to the service manual to confirm component ratings and circuit operation
(Award 1 mark for correct use of documentation)
1
Sub-Total16
PRODUCT CHECKLIST
Correctly identified all main starter components with clear and accurate explanations
(Award up to 8 marks for completeness and accuracy of identification and explanation)
8
Accurate readings and verification of component specifications using measuring instruments
(Award up to 5 marks for correct measurements and interpretation)
5
Neat and clear labeling or arrangement of components as per standard practice
(Award up to 4 marks for professional presentation and labeling)
4
Sub-Total17
GRAND TOTAL33
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Wire an autotransformer starter control circuit for a 3-phase asynchronous motor

Refrigeration And Air Conditioning · Level 6
Electrical Motor Control Principles
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Wire an autotransformer starter control circuit for a 5 HP, 3-phase asynchronous motor.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Insulated screwdriver set3-phase asynchronous motor (5 HP)
Wire strippers and cuttersAutotransformer starter kit
Digital multimeterControl panel enclosure
Insulation testerInsulated copper wires
PliersElectrical tape
Clamp meterRelays
Service manual
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
13-phase asynchronous motor (5 HP)1 Pc per Candidate
2Autotransformer starter kit (including autotransformer, contactors, overload relay)1 Set per Candidate
3Control panel enclosure (metallic)1 Pc per Candidate
4Insulated copper wires (various sizes)10 m per Candidate
5Insulated screwdriver set1 Set per Candidate
6Wire strippers and cutters1 Set per Candidate
7Digital multimeter1 Pc per Candidate
8Insulation tester (megger)1 Pc per Candidate
9Pliers1 Pc per Candidate
10Electrical tape1 Roll per Candidate
11Clamp meter1 Pc per Candidate
12Relays (control relays)1 Set per Candidate
13Service manual for autotransformer starter1 Pc per Candidate
14Personal protective equipment (safety boots, gloves, apron, goggles)1 Set per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Preparation and Safety
Wore appropriate PPE including safety boots, gloves, apron, and goggles
(Award 1 mark for correct PPE worn, zero otherwise)
1
Handled tools and equipment as per workshop safety procedures
(Award 1 mark for correct and safe tool handling)
1
Checked and interpreted the autotransformer starter schematic diagram correctly
(Award 1 mark for correct interpretation of circuit diagram)
1
Sub-Total3
TASK 2: Wiring and Connection
Selected correct wire sizes and colors as per standards
(Award 1 mark for correct wire selection)
1
Connected autotransformer, contactors, overload relay, and motor terminals correctly
(Award up to 3 marks for correct and neat connections)
3
Installed control relays and auxiliary contacts as per circuit requirements
(Award 1 mark for correct relay installation)
1
Used appropriate wire stripping, cutting and termination techniques
(Award 1 mark for proper wire preparation techniques)
1
Secured wiring inside the control panel enclosure neatly and safely
(Award 1 mark for neat and safe wiring inside enclosure)
1
Sub-Total7
TASK 3: Testing and Commissioning
Tested continuity and insulation resistance of wiring using multimeter and insulation tester
(Award 1 mark for correct testing and reading interpretation)
1
Tested operation of control circuit including start/stop push buttons and relays
(Award 1 mark for functional control circuit test)
1
Measured voltage and current during motor start using clamp meter
(Award 1 mark for correct measurement and interpretation)
1
Debugged and corrected any wiring faults found during testing
(Award 1 mark for fault diagnosis and correction)
1
Sub-Total4
TASK 4: Housekeeping and Reporting
Performed workplace housekeeping: cleaned work area, tools, and disposed waste as per policy
(Award 1 mark for proper housekeeping)
1
Prepared a service report including task title, tools used, faults identified, and procedure followed
(Award 1 mark for complete and clear service report)
1
Sub-Total2
PRODUCT CHECKLIST
Autotransformer starter control circuit wiring is correct, neat, and fully functional
(Award up to 5 marks for correct wiring, neatness, and successful operation)
5
Wiring and connections comply with the provided schematic diagram and safety standards
(Award 3 marks for compliance with schematic and standards)
3
Wiring insulation resistance and continuity tests meet acceptable values (minimum 1 MΩ insulation resistance)
(Award 2 marks for passing insulation and continuity tests)
2
Sub-Total10
GRAND TOTAL26
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Debugging and Repair of Autotransformer Starter Control Circuit for a 5HP Three-Phase Asynchronous MotorPractical 3
🔒Test Autotransformer Starter Circuit Operation for a 3-Phase Asynchronous MotorPractical 4
🔒Diagnose faults in a three-phase autotransformer starter control circuitPractical 5
🔒Perform insulation resistance test on an autotransformer reduced-voltage starter circuitPractical 6
🔒Interpret Diagnostic Test Results of Autotransformer Starter Control CircuitPractical 7
🔒Write a diagnosis report on an auto transformer starter control circuitPractical 8
🔒Oral Presentation of Auto Transformer Starter Diagnosis ReportPractical 9
Flashcards 20 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

18 more in this section.

Create a free account
Test Yourself 18 questions Start quiz ▾
0%
0 / 2
🔒

16 more in this section.

Create a free account
Am I competent?

At the start of this chapter we promised you would be able to:

  • Apply the principles and methods of autotransformer reduced-voltage starter circuits for three-phase asynchronous motors based on starter control job needs.
  • Correctly connect autotransformer reduced-voltage starter circuits following the proper procedures.
  • Safely debug autotransformer reduced-voltage starter circuits to ensure they work as intended.
  • Accurately diagnose issues in autotransformer reduced-voltage starter circuits using job requirements and manufacturer specifications.
  • Prepare a clear and professional diagnosis report following workplace procedures.

Tick each one you can genuinely do.

So, are you there yet?

You're competent when you can confidently do 50% or more of what this chapter promised.

Sign in to record how you're doing.