Refrigeration And Air Conditioning  ·  Level 6
Electrical Motor Control Principles
Chapter 6: Operate double star-type reduced voltage starter circuits
📚 4 Topics
⚑ What you will be able to do

By the end of this chapter, you will be able to:
- apply the principles and methods of Y-type reduced-voltage starter circuits for star-type three-phase asynchronous motors safely and correctly according to IEC 6092 standards.
- connect and debug Y-type reduced-voltage starter circuits of three-phase asynchronous motors accurately following IEC 60034 standards.
- diagnose double Y-type reduced-voltage starter circuits of three-phase asynchronous motors effectively according to job requirements and manufacturer’s specifications.
- prepare detailed and clear diagnosis reports following workplace procedures.

Mastering these skills will help you confidently handle motor control systems, ensuring safe and efficient operation in real electrical trade environments.

Operating double star-type reduced voltage starter circuits is a fundamental skill in controlling three-phase asynchronous motors, widely used across Kenyan industries such as hospitals, banks, county offices, and farms. This chapter explores the principles and methods employed in Y-type reduced-voltage starting to ensure smooth motor acceleration while minimizing mechanical stress and electrical surges. Understanding these starter circuits enhances operational safety and efficiency in diverse professional environments where motor-driven equipment is critical for service delivery and productivity.

6.1 Principle and method of Y-type reduced-voltage starter circuits of three-phase asynchronous motor

6.1.1 Principle of Y-type reduced-voltage starter circuits

The Y-type reduced-voltage starter circuit is designed to reduce the starting current and torque of a three-phase asynchronous motor by initially connecting the motor windings in a star (Y) configuration instead of the usual delta (Δ) configuration. This method limits the voltage applied to each phase winding to approximately 58% of the full line voltage, which significantly reduces the inrush current during motor start-up.

Key aspects of the Y-type starter principle

  • Voltage Reduction: Connecting the motor windings in star reduces the phase voltage to line voltage divided by √3, which is approximately 58% of the line voltage. This lowers the starting current and torque proportionally.
  • Current Limitation: The reduced voltage causes the motor to draw less starting current, typically about one-third of the current that would be drawn if started directly on line, protecting the electrical supply network from voltage dips.
  • Torque Reduction: Because torque is proportional to the square of the voltage, the motor produces about one-third of the starting torque, which decreases mechanical stress on the motor shaft and driven equipment.
  • Automatic Transition: After the motor reaches a certain speed, the starter switches the connection from star to delta, applying full line voltage for normal operation.
  • Protection of Electrical Components: This starting method minimizes the risk of damage to the motor windings and connected electrical devices by avoiding high inrush currents.

In practice, a county referral hospital using large ventilation fans benefits from the Y-type starter by preventing voltage fluctuations that could disrupt sensitive medical equipment during motor start-up.

6.1.2 Components and configuration of Y-type reduced-voltage starter circuits

A Y-type starter circuit comprises several key electrical components arranged to facilitate the automatic transition from star to delta connection. Understanding these components and their configuration is essential for proper operation and maintenance.

Components of a Y-type reduced-voltage starter

  • Contactors: Three contactors are used, one for the star connection, one for the delta connection, and one main contactor for line supply. They control the switching of motor windings between star and delta configurations.
  • Timer Relay: This device controls the duration the motor remains in star connection before switching to delta, ensuring the motor reaches adequate speed.
  • Overload Relay: Protects the motor from overheating due to excessive current by disconnecting power if an overload condition persists.
  • Control Circuit: Includes push buttons for start and stop, auxiliary contacts, and interlocks that prevent simultaneous closing of star and delta contactors.
  • Power Supply Lines: Three-phase supply lines connected through the main contactor to the motor via star and delta contactors.

Configuration layout

  • Initially, the main contactor and star contactor close, energizing the motor windings in star configuration.
  • After the preset time, the star contactor opens while the delta contactor closes, reconfiguring the motor windings into delta for full voltage operation.
  • Interlocking mechanisms ensure that star and delta contactors cannot close simultaneously, preventing short circuits.

6.1.3 Method of starting and switching in Y-type reduced-voltage starter circuits

The procedure for starting a motor with a Y-type reduced-voltage starter involves a controlled sequence to ensure safe transition between reduced and full voltage operation, safeguarding both electrical and mechanical components.

Step-by-step method for operating a Y-type starter

  1. Initiate Start Command: The operator presses the start button, energizing the main and star contactors.
  2. Star Connection Energized: Motor windings are connected in star, applying reduced voltage to limit current and torque.
  3. Timer Activation: The timer relay begins counting down the preset delay time, allowing the motor to accelerate smoothly.
  4. Transition to Delta: Once the timer elapses, the star contactor opens, and the delta contactor closes, switching the motor windings to delta configuration.
  5. Full Voltage Operation: The motor now runs at full line voltage, delivering rated torque and speed.
  6. Stop Operation: Pressing the stop button de-energizes all contactors, safely stopping the motor.

This method is commonly implemented in county government water pumping stations where gradual motor start-up prevents water hammer and pressure surges in pipelines.

6.1.4 Advantages and limitations of Y-type reduced-voltage starter circuits

The Y-type starter is widely used due to its simplicity and effectiveness in reducing starting current, but it also presents certain limitations that must be considered in professional settings.

Advantages of Y-type starters

  • Reduced Starting Current: Limits inrush current to about one-third of direct-on-line starting, protecting electrical network stability.
  • Decreased Mechanical Stress: Lower starting torque reduces wear on motor shafts and connected machinery, extending equipment lifespan.
  • Cost-Effectiveness: Compared to more complex soft starters or variable frequency drives, Y-type starters are economical and easy to maintain.
  • Simplicity: The design and control circuit are straightforward, making troubleshooting and repairs manageable in facilities like universities or SACCO offices.
  • Compatibility: Suitable for motors that do not require high starting torque, widely applicable across various industries.

Limitations of Y-type starters

  • Reduced Starting Torque: The approximately one-third torque may be insufficient for heavy load applications, causing the motor to stall or fail to start.
  • Mechanical Shock During Switching: The transition from star to delta can cause torque surges, potentially damaging delicate load equipment.
  • Not Suitable for All Motors: Motors designed for direct-on-line starting with high starting torque needs may not perform well with Y-type starters.
  • Fixed Transition Time: Timer-based switching does not adapt to varying load conditions, which can affect performance.
  • Additional Wiring Complexity: Requires more wiring and control components than direct-on-line starters, increasing installation time.

Practice Questions

  1. Explain how the voltage applied to motor windings is reduced in a Y-type starter and describe the effect on starting current and torque. (10 marks)
  2. List and describe the main components of a Y-type reduced-voltage starter circuit. (10 marks)
  3. Outline the step-by-step method of starting a motor using a Y-type starter. (12 marks)
  4. Discuss five advantages and five limitations of using Y-type reduced-voltage starters in industrial applications. (15 marks)
The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒6.2 Connection and debugging methods of Y-type reduced-voltage starter circuits of three-phase asynchronous motor

In many Kenyan institutions such as county referral hospitals, manufacturing firms, and large hotels, three-phase asynchronous motors are widely used to drive pumps, compressors, and other heavy equipment. The Y-type (star) reduced-voltage starter is a common…

🔒6.3 Diagnosis of double Y-type reduced-voltage starter circuits of three-phase asynchronous motor

In many Kenyan industries such as county government water supply departments or large-scale agricultural processing plants, three-phase asynchronous motors are widely used due to their robustness and efficiency. The double Y-type reduced-voltage starter circui…

🔒6.4 Writing diagnosis reports

In Kenya's diverse professional environments, the ability to write clear and accurate diagnosis reports for electrical motor control systems is essential. Whether working in a county hospital's maintenance department, a university's facilities unit, or a retai…

Chapter Summary

This chapter explored the principle and method of Y-type reduced-voltage starter circuits used in three-phase asynchronous motors, explaining how these circuits reduce the starting current by initially connecting the motor windings in a star configuration. The connection and debugging methods were detailed, emphasizing the correct wiring procedures and troubleshooting techniques to ensure the starter circuit operates safely and efficiently. It also covered the diagnosis of double Y-type reduced-voltage starter circuits, focusing on identifying common faults and operational issues that can arise during motor startup. The chapter concluded with guidance on writing diagnosis reports, highlighting the importance of clear documentation, accurate fault description, and recommended corrective actions to support maintenance and repair activities. Together, these topics provide a comprehensive understanding of operating and maintaining Y-type reduced-voltage starter circuits in industrial motor control applications.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. What is the primary purpose of a Y-type reduced-voltage starter in a three-phase asynchronous motor? (2 marks)
  2. Identify two advantages of using Y-type reduced-voltage starters in industrial motor applications. (4 marks)
🔒20 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Explain the principle of Y-type reduced-voltage starting in a three-phase asynchronous motor and why it is preferred in industries such as county hospitals. (4 marks)
  2. Describe the key steps involved in connecting a Y-type reduced-voltage starter circuit for a three-phase asynchronous motor in a university workshop. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Demonstrate and explain the principle of Y-type reduced-voltage starter for a three-phase asynchronous motor

Refrigeration And Air Conditioning · Level 6
Electrical Motor Control Principles
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Explain the principle of a Y-type reduced-voltage starter circuit using a three-phase asynchronous motor model and a circuit diagram measuring 300mm x 200mm.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Digital multimeterThree-phase asynchronous motor model
Insulated screwdriver setY-type reduced-voltage starter circuit diagram (300mm x 200mm)
PliersElectrical tape
Wire strippers and cutters
Clamp meter
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Three-phase asynchronous motor model1 Pc per Candidate
2Y-type reduced-voltage starter circuit diagram (printed A3 size)1 Pc per Candidate
3Digital multimeter1 Pc per Candidate
4Insulated screwdriver set1 Set per Candidate
5Pliers1 Pc per Candidate
6Wire strippers and cutters1 Pc per Candidate
7Electrical tape1 Roll per Candidate
8Clamp meter1 Pc per Candidate
9Safety boots1 Pair per Candidate
10Safety gloves1 Pair per Candidate
11Safety goggles1 Pair per Candidate
12Overall/dust coat1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Demonstrate and explain the Y-type reduced-voltage starter principle
Wore appropriate PPE as per job requirements: overall/dust coat, safety boots, gloves, goggles
(Award 1 mark for correct PPE usage or zero)
1
Handled tools and equipment correctly as per workshop procedures and safety standards
(Award 1 mark for correct tool handling or zero)
1
Identified and explained the main components of the Y-type reduced-voltage starter circuit using the diagram
(Award up to 3 marks for clear and correct identification and explanation)
3
Demonstrated the working principle of the Y-type starter by tracing current flow through the motor model
(Award up to 4 marks for accurate demonstration and explanation)
4
Used measuring instruments (multimeter and clamp meter) to show voltage and current changes during motor start-up
(Award up to 3 marks for correct and safe use of instruments and interpretation of readings)
3
Explained advantages and limitations of the Y-type reduced-voltage starter method
(Award up to 3 marks for comprehensive explanation)
3
Maintained a clean and safe working area throughout the practical
(Award 1 mark for good housekeeping or zero)
1
Sub-Total16
PRODUCT CHECKLIST
Clear and correctly labeled Y-type reduced-voltage starter circuit diagram (300mm x 200mm)
(Award up to 3 marks for accuracy, clarity, and completeness)
3
Accurate demonstration of motor model showing correct wiring and operation according to Y-type starter principle
(Award up to 4 marks for correct wiring and operational demonstration)
4
Correct measurement readings of voltage and current during motor start-up documented
(Award up to 2 marks for correct and relevant measurement readings)
2
Sub-Total9
GRAND TOTAL25
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Assemble Y-Type Reduced-Voltage Starter Circuit for Three-Phase Asynchronous Motor

Refrigeration And Air Conditioning · Level 6
Electrical Motor Control Principles
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Assemble and wire a Y-type reduced-voltage starter circuit for a 3-phase asynchronous motor (5 HP, 400 V).
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Insulated screwdriver setThree-phase asynchronous motor (5 HP, 400 V)
Wire strippers and cuttersY-type reduced-voltage starter kit
Digital multimeterControl transformer (230 V/24 V)
PliersThermal overload relay
Electrical tapeControl push buttons (Start and Stop)
Insulated copper wires (1.5 mm² and 2.5 mm²)
Terminal connectors and ferrules
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Three-phase asynchronous motor (5 HP, 400 V)1 Pc per Candidate
2Y-type reduced-voltage starter kit (including contactors, overload relay, and auxiliary contacts)1 Set per Candidate
3Control transformer (230 V/24 V)1 Pc per Candidate
4Thermal overload relay (rated for 5 HP motor)1 Pc per Candidate
5Control push buttons (Start and Stop)1 Set per Candidate
6Insulated copper wires (1.5 mm² and 2.5 mm²)3 meters per Candidate
7Insulated screwdriver set1 Set per Candidate
8Wire strippers and cutters1 Pc per Candidate
9Digital multimeter1 Pc per Candidate
10Electrical tape1 Roll per Candidate
11Pliers1 Pc per Candidate
12Terminal connectors and ferrulesEnough per Candidate
13Safety gloves1 Pair per Candidate
14Safety boots1 Pair per Candidate
15Dust coat/overall1 Pc per Candidate
16Safety goggles1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Preparation and Safety
Wore appropriate PPE including dust coat/overall, safety boots, gloves, and safety goggles
(Award 1 mark for correct PPE worn, zero otherwise)
1
Handled tools safely and correctly according to workshop procedures
(Award 1 mark for safe and proper tool use)
1
Verified motor and starter specifications against circuit diagram
(Award 1 mark for correct verification)
1
Checked all components for damage or defects before assembly
(Award 1 mark for thorough inspection)
1
Identified correct wiring layout and terminal markings on starter components
(Award 1 mark for correct identification)
1
Prepared workspace and materials in an organized manner
(Award 1 mark for good workspace preparation)
1
Sub-Total6
TASK 2: Assembly and Wiring
Connected control transformer and verified correct voltage output
(Award 2 marks for proper connection and voltage verification)
2
Installed and wired the Y-type starter contactors as per circuit diagram
(Award 3 marks for correct wiring and secure connections)
3
Connected thermal overload relay correctly in the circuit
(Award 2 marks for proper placement and wiring)
2
Wired start and stop push buttons into the control circuit
(Award 2 marks for correct wiring and operation)
2
Connected motor terminals in Y-configuration for reduced voltage starting
(Award 3 marks for proper motor connection)
3
Used appropriate wire sizes and correctly terminated wires using ferrules
(Award 2 marks for correct wire sizing and termination)
2
Applied electrical tape and secured all connections neatly
(Award 1 mark for neat finishing)
1
Sub-Total15
TASK 3: Testing and Commissioning
Performed continuity and insulation resistance tests on wiring
(Award 2 marks for accurate testing and interpretation)
2
Checked motor windings and starter coil for correct resistance values
(Award 2 marks for correct measurement and evaluation)
2
Verified correct operation of start and stop push buttons
(Award 1 mark for functional control buttons)
1
Conducted a no-load test run of the motor starter assembly
(Award 3 marks for safe and successful test run)
3
Monitored motor starting current and ensured reduced voltage starting
(Award 2 marks for correct current observation)
2
Recorded test results and faults (if any) in the service report
(Award 2 marks for complete and clear documentation)
2
Sub-Total12
TASK 4: Housekeeping
Cleaned the work area and disposed of waste materials properly
(Award 1 mark for thorough cleaning)
1
Stored tools and unused materials in designated places
(Award 1 mark for proper storage)
1
Prepared and submitted a service report compliant with workplace and OSHA standards
(Award 2 marks for complete and accurate report)
2
Sub-Total4
PRODUCT CHECKLIST
Y-type reduced-voltage starter circuit assembled as per provided circuit diagram
(Award 3 marks for correct assembly and wiring)
3
Motor connected in Y-configuration with correct terminal identification
(Award 3 marks for correct motor connection)
3
Starter components securely mounted and wiring neatly arranged
(Award 2 marks for workmanship and neatness)
2
Circuit tested successfully showing reduced voltage starting of the motor
(Award 4 marks for successful functional test)
4
Circuit measurements match the specifications: motor 5 HP, 400 V, starter rated accordingly
(Award 3 marks for compliance with specifications)
3
Sub-Total15
GRAND TOTAL52
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Debugging and Testing a Y-type Reduced-Voltage Starter Circuit for a 3-Phase Asynchronous MotorPractical 3
🔒Assemble double Y-type reduced voltage starter circuit for a 3-phase motorPractical 4
🔒Diagnose faults in a double Y-type reduced-voltage starter circuit for a three-phase asynchronous motorPractical 5
🔒Write a detailed diagnosis report for faults in a double Y-type reduced-voltage starter circuitPractical 6
🔒Test Motor Performance with Y-Type Reduced-Voltage StarterPractical 7
🔒Demonstrate safety and operational procedures for Y-type startersPractical 8
🔒Maintain and clean double Y-type reduced-voltage starter circuit for a 3-phase asynchronous motorPractical 9
Flashcards 20 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

18 more in this section.

Create a free account
Test Yourself 18 questions Start quiz ▾
0%
0 / 2
🔒

16 more in this section.

Create a free account
Am I competent?

At the start of this chapter we promised you would be able to:

  • apply the principles and methods of Y-type reduced-voltage starter circuits for star-type three-phase asynchronous motors safely and correctly according to IEC 6092 standards.
  • connect and debug Y-type reduced-voltage starter circuits of three-phase asynchronous motors accurately following IEC 60034 standards.
  • diagnose double Y-type reduced-voltage starter circuits of three-phase asynchronous motors effectively according to job requirements and manufacturer’s specifications.
  • prepare detailed and clear diagnosis reports following workplace procedures.

Tick each one you can genuinely do.

So, are you there yet?

You're competent when you can confidently do 50% or more of what this chapter promised.

Sign in to record how you're doing.