Electronics Engineering  ·  Level 6
Electrical Principles II
Chapter 2: Apply three phase power supply
📚 4 Topics
⚑ What you will be able to do

By the end of this chapter, you will be able to:

  • Safely construct simple cells by following the correct work procedures.
  • Identify different types of cells and batteries needed for various electrical jobs.
  • Accurately determine the E.M.F and internal resistance of cells using proper measurement techniques.
  • Carry out battery maintenance correctly, following the manufacturer’s specifications.
  • Identify the applications of batteries that are relevant to specific work requirements.

Mastering these skills will help you confidently handle batteries and cells in real electrical projects, ensuring safety and reliability in your trade.

Three phase power supply forms the backbone of modern electrical distribution systems, delivering efficient and reliable power to diverse sectors across Kenya. Understanding its principles and configurations equips diploma-level graduates with essential knowledge to manage, troubleshoot, and optimize electrical systems in environments ranging from county referral hospitals to large retail complexes. This chapter explores the fundamental concepts of three phase power generation and the common methods of connecting three phase supplies, enabling students to apply these principles in various professional fields.

2.1 Principles of Three Phase Power Generation

The generation of three phase power involves producing three alternating currents that are equal in frequency and amplitude but phase-shifted by 120 degrees. This method provides a steady and balanced power flow, essential for industrial and commercial applications where consistent energy supply is critical. In Kenya, institutions like county government offices and universities rely on three phase power to operate heavy machinery, air conditioning systems, and computer labs efficiently.

2.1.1 Nature of Three Phase Alternating Current

Three phase alternating current (AC) consists of three sinusoidal voltages of equal magnitude and frequency, each displaced in time by one-third of a cycle or 120 degrees. This phase displacement ensures that at any instant, the sum of the instantaneous voltages equals zero, providing a balanced system. The continuous power transfer in three phase systems reduces pulsations common in single-phase systems, making it ideal for powering sensitive equipment in hospitals and banks.

2.1.2 Generation of Three Phase Voltage

The generation of three phase voltage is achieved by rotating a coil within a magnetic field or rotating a magnetic field around stationary coils arranged at 120 degrees apart on the stator of a generator. This mechanical rotation induces electromotive forces (EMFs) in each coil, producing three sinusoidal voltages separated by 120 electrical degrees. For example, at a university power plant, the rotor’s mechanical energy, often from steam or hydro turbines, is converted into electrical energy in this manner.

2.1.3 Advantages of Three Phase Power Generation

Three phase power generation offers several advantages over single phase systems, including:

Advantages of Three Phase Power Generation

  • Higher Power Density: Three phase systems deliver more power than single phase systems of the same current rating, supporting large loads at institutions like county hospitals without requiring oversized conductors.
  • Constant Power Delivery: The power output remains constant over each cycle, minimizing vibrations in motors and improving the lifespan of equipment used in manufacturing cooperatives.
  • Efficient Transmission: Reduced conductor material is needed for the same power transfer, lowering infrastructure costs for retail businesses and SACCOs.
  • Self-Starting Motors: Three phase motors start without additional starting mechanisms, enhancing reliability in hotel air conditioning systems.
  • Balanced Load Distribution: The load can be evenly distributed across three phases, reducing the risk of overloading and improving system stability in county government offices.

2.1.4 Frequency and Voltage Standards in Kenya

In Kenya, three phase power is supplied at a standard frequency of 50 Hz, with typical line voltages of 415 V between phases and 240 V between phase and neutral. Adhering to these standards ensures compatibility of equipment and safety in various sectors such as educational institutions and financial firms. Deviations from these standards can cause equipment malfunction or damage, underscoring the importance of proper system design and maintenance.

Practice Questions

  1. Explain why three phase power delivery results in constant power output while single phase does not. (5 marks)
  2. Describe the process by which three phase voltage is generated in an alternator. (6 marks)
  3. List and explain five advantages of three phase power generation in commercial settings. (10 marks)
  4. What are the standard frequency and voltage levels for three phase power supply in Kenya? Why is adherence to these standards important? (4 marks)
The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒2.2 Connections of Three Phase Power Supply

The configuration of three phase power connections directly influences the performance and suitability of electrical systems for different applications. Two primary connection methods, star (Y) and delta (Δ), are widely used to connect generators, transformers…

🔒2.3 Calculations involving three phase power supply connections

Understanding calculations related to three phase power supply connections is essential for professionals in various Kenyan industries such as county hospitals, universities, retail businesses, and agriculture cooperatives. Accurate calculations ensure efficie…

🔒2.4 Measurements of three phase power supply

Measuring power in three phase systems is fundamental for electrical maintenance and management in diverse Kenyan sectors such as banks, hospitals, and educational institutions. Proper measurement techniques ensure accurate billing, system monitoring, and faul…

Chapter Summary

This chapter explored the fundamental principles of three phase power generation, explaining how three separate alternating currents are produced with a phase difference of 120 degrees to ensure efficient power delivery. It detailed the two primary types of three phase power supply connections, star and delta, highlighting their structural differences and implications for voltage and current in electrical systems. The chapter also covered essential calculations related to three phase power supply connections, enabling accurate determination of power, voltage, and current in both star and delta configurations. Measurement techniques for three phase power supply were examined, focusing on the one wattmeter, two wattmeter, and three wattmeter methods, each suited to different system conditions and load types. These methods provide practical means to assess power consumption and system performance in three phase circuits. Understanding these concepts is crucial for effective design, operation, and maintenance of electrical power systems in various industrial and commercial settings.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. What is the fundamental principle behind three phase power generation? (2 marks)
  2. Describe the main difference between star and delta connections in a three phase system. (3 marks)
🔒20 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Explain the principle of three phase power generation and how it benefits power supply at a county referral hospital. (4 marks)
  2. Differentiate between star and delta connections in three phase supply with reference to their typical applications in a university power system. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Demonstrate principles of three phase power generation using a model

Electronics Engineering · Level 6
Electrical Principles II
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Set up and demonstrate operation of a three phase power generation model on a 500mm x 400mm mounting board.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Insulated screwdriversThree phase synchronous generator model 415 V, 50 Hz
MultimeterThree phase load bank (resistive)
Connecting leadsThree phase voltage and current meter set
Switching board with isolator
PPE (Safety gloves, goggles, safety boots)
3-phase model mounting board (500mm x 400mm)
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Three phase synchronous generator model 415 V, 50 Hz1 Pc per Candidate
2Three phase load bank (resistive)1 Pc per Candidate
3Three phase voltage and current meter set1 set per Candidate
4Connecting leads (4 mm2, red, yellow, blue, black)5 m per Candidate
5Switching board with isolator1 Pc per Candidate
6Instruction manual and circuit diagram sheet A41 Pc per Candidate
7PPE (Safety gloves, goggles, safety boots)1 set per Candidate
8Insulated screwdrivers1 Pc per Candidate
9Multimeter1 Pc per Candidate
103-phase model mounting board (500mm x 400mm)1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Setup and demonstration of three phase power generation model
Wore personal protective equipment (gloves, goggles, boots)
(Award 2 marks if all PPE worn correctly, else 0)
2
Listed and prepared all necessary tools and materials
(Award 3 marks if all tools/materials listed and ready)
3
Connected the three phase synchronous generator model as per circuit diagram
(Award 5 marks for correct and safe connections)
5
Connected the load bank correctly to the model
(Award 4 marks for correct load connection)
4
Installed and connected the voltage and current meters properly
(Award 3 marks for correct meter installation)
3
Used the isolator switch correctly to power the model
(Award 3 marks for correct use of isolator switch)
3
Demonstrated operation by showing voltage and current readings on meters
(Award 5 marks for clear demonstration and explanation)
5
Explained the principles of three phase power generation during demonstration
(Award 5 marks for accurate and clear explanation)
5
Performed safe disconnection and housekeeping after demonstration
(Award 3 marks for safe shutdown and clean working area)
3
Sub-Total33
PRODUCT CHECKLIST
Model setup matches provided circuit diagram with correct wiring and connections
(Award 5 marks if wiring and connections are correct and neat)
5
Operating readings show balanced three phase voltages approximately 415 V ±5%
(Award 4 marks if voltages are balanced within tolerance)
4
Current readings show load current as per load bank rating
(Award 3 marks if current readings correspond to load)
3
Mounting board is neat and components fixed firm and level (500mm x 400mm)
(Award 3 marks if components are firmly fixed and neat)
3
Sub-Total15
GRAND TOTAL48
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Identify and connect three phase power supply terminals

Electronics Engineering · Level 6
Electrical Principles II
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Connect and label the three phase power supply terminals of a 415 V, 50 Hz induction motor on a 1m by 1m installation board as per the provided wiring diagram.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Lug Crimping Tool3-phase Induction Motor 415 V, 50 Hz
Electrician Toolkit (Screwdrivers, Pliers, Side Cutter)3 Phase Isolator 415 V AC
PPE (Gloves, Goggles, Safety Boots)PVC singles R/B/Y/G cable 4.0 mm2
Cable ClipsLabels/Tags
Cable Fork Lugs
Vertical Wooden Installation Board 1m x 1m
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
13-phase Induction Motor 415 V, 50 Hz1 Pc per Candidate
23 Phase Isolator 415 V AC1 Pc per Candidate
3PVC singles R/B/Y/G cable 4.0 mm24 m per Candidate
4Labels/Tags1 set per Candidate
5Cable Fork Lugs 4.0 mm2Enough per Candidate
6Lug Crimping Tool1 Pc per Candidate
7Electrician Toolkit (Screwdrivers, Pliers, Side Cutter)1 set per Candidate
8PPE (Gloves, Goggles, Safety Boots)1 set per Candidate
9Cable Clips 12 mm1 pkt per Candidate
10Vertical Wooden Installation Board 1m x 1m1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Preparation and Safety
Wore appropriate personal protective equipment (gloves, goggles, safety boots)
(Award 2 marks for correct PPE worn, 0 if not)
2
Listed and assembled all required tools and materials
(Award 3 marks for complete and correct tools and materials)
3
Ensured clean and safe working area before commencing work
(Award 1 mark for good housekeeping)
1
Observed correct colour coding for three phase cables (R-Red, Y-Yellow, B-Blue, G-Green Earth)
(Award 2 marks for correct colour code observed, 0 if incorrect)
2
Sub-Total8
TASK 2: Connection and Labelling
Connected the three phase cables correctly to the motor terminals
(Award 5 marks for correct and secure connections)
5
Connected the three phase cables correctly to the isolator terminals
(Award 5 marks for correct and secure connections)
5
Used cable lugs and crimped securely without damaging cables
(Award 4 marks for proper lug crimping and cable handling)
4
Fixed cables neatly on the installation board using cable clips at correct spacing (~150 mm)
(Award 3 marks for neat cable fixing and correct clip spacing)
3
Correctly labelled each terminal and cable according to phase and earth
(Award 3 marks for clear and correct labelling)
3
Sub-Total20
TASK 3: Testing and Final Checks
Performed continuity test on all connections
(Award 4 marks for proper continuity test and result)
4
Performed insulation resistance test
(Award 4 marks for proper insulation test and result)
4
Verified polarity and phase sequence
(Award 4 marks for correct polarity and phase sequence)
4
Ensured final connections are firm and no loose wires
(Award 3 marks for firm and safe connections)
3
Performed good housekeeping after completion
(Award 2 marks for cleaning the work area and proper tool storage)
2
Sub-Total17
PRODUCT CHECKLIST
Finished installation board with correctly connected and labelled three phase terminals; cables fixed neatly; dimensions 1000 mm x 1000 mm verified
(Award 15 marks for accuracy of connections, neatness, and correct labelling and dimensions)
15
Sub-Total15
GRAND TOTAL60
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Construct and test a three phase star connectionPractical 3
🔒Construct and Test a Three Phase Delta ConnectionPractical 4
🔒Calculate line and phase voltages and currents in three phase systemsPractical 5
🔒Measure three phase voltage and current in an industrial supplyPractical 6
🔒Measure power in a balanced three-phase circuit using one wattmeter methodPractical 7
🔒Measure power in a three-phase system using the two wattmeter methodPractical 8
🔒Apply Three Wattmeter Method to Measure Power in an Unbalanced Three Phase SystemPractical 9
🔒Compare power measurement methods in three phase systemsPractical 10
Flashcards 20 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

18 more in this section.

Create a free account
Test Yourself 16 questions Start quiz ▾
0%
0 / 2
🔒

14 more in this section.

Create a free account
Am I competent?

At the start of this chapter we promised you would be able to:

  • Safely construct simple cells by following the correct work procedures.
  • Identify different types of cells and batteries needed for various electrical jobs.
  • Accurately determine the E.M.F and internal resistance of cells using proper measurement techniques.
  • Carry out battery maintenance correctly, following the manufacturer’s specifications.
  • Identify the applications of batteries that are relevant to specific work requirements.

Tick each one you can genuinely do.

So, are you there yet?

You're competent when you can confidently do 50% or more of what this chapter promised.

Sign in to record how you're doing.