Biomedical Engineering  ·  Level 5
Hospital Plant And Building Services II
Chapter 2: Maintain medical gases
📚 6 Topics
⚑ What you will be able to do

By the end of this chapter, you will be able to:

  • Follow health hazard and safety procedures correctly according to water system guidelines.
  • Inspect water system components carefully by following proper work procedures.
  • Clean water system equipment properly and safely according to work procedures.
  • Perform fault diagnosis on water system equipment accurately using the service manual.
  • Maintain and repair faulty parts of water system equipment correctly following manufacturer’s specifications.
  • Calibrate water systems precisely according to the manufacturer’s instructions.
  • Conduct a full water system functionality check following the service manual.
  • Provide clear and effective user training based on the equipment user manual.
  • Prepare detailed and accurate water systems service reports following correct work procedures.

Mastering these skills ensures that medical gas systems operate safely and reliably, which is vital for patient care and hospital safety.

Medical gases such as oxygen are critical in healthcare delivery, supporting life-saving interventions and routine patient care. Biomedical engineers in Kenya play a vital role in ensuring the availability, purity, and safety of these gases by maintaining production equipment and systems. This chapter focuses on the fundamental technologies used to produce medical gases, particularly oxygen, which is the most commonly used therapeutic gas. Understanding these production methods is essential for effective maintenance, troubleshooting, and optimization of hospital plant and building services.

2.1 Basics of Oxygen Production

Oxygen production technologies vary in complexity and scale, from onsite generation units to bulk supply from industrial gas suppliers. Biomedical engineers in Kenyan hospitals and clinics must be familiar with the principles and maintenance requirements of each system to guarantee uninterrupted oxygen supply. These technologies include Pressure Swing Adsorption (PSA), Cryogenic Air Separation, Vacuum Swing Adsorption (VSA), Electrolysis of Water, and Chemical Methods. Each method has distinct operational characteristics, advantages, and maintenance considerations relevant to different healthcare facility contexts.

2.1.1 Pressure Swing Adsorption (PSA)

Pressure Swing Adsorption (PSA) is widely used in hospitals for onsite oxygen generation because it offers a reliable and cost-effective solution without dependence on liquid oxygen deliveries. PSA units separate oxygen from atmospheric air by exploiting the differential adsorption properties of gases on zeolite materials under varying pressures.

Principle of PSA Operation

PSA technology relies on the selective adsorption of nitrogen by zeolite molecular sieves under high pressure, allowing oxygen to pass through as the primary product gas. The process cycles between two vessels filled with zeolite: one adsorbs nitrogen at high pressure while the other regenerates at low pressure by releasing nitrogen back into the atmosphere. This cyclic pressurization and depressurization produce a continuous stream of oxygen enriched to 90-95% purity.

Components of a PSA Oxygen Plant

A typical PSA oxygen generator consists of air compressors, pre-filters, adsorption towers containing zeolite, pressure regulators, control valves, and oxygen storage tanks. The air compressor supplies clean, dry compressed air to the adsorption towers. Pre-filters remove oil, dust, and moisture to protect the zeolite beds. Valves and control systems manage the timing and pressure changes during adsorption and regeneration cycles.

Maintenance Requirements for PSA Systems

Regular maintenance of PSA plants is critical to ensure oxygen purity and system longevity. Key maintenance tasks include monitoring and replacing air filters to prevent contamination, checking compressor oil levels and condition, inspecting zeolite beds for degradation, and verifying valve operation to maintain correct pressure cycling. Calibration of oxygen analyzers and pressure sensors is essential to detect performance deviations early.

Challenges and Troubleshooting in PSA Systems

Common issues in PSA units include reduced oxygen purity due to zeolite fouling or air leaks, compressor failure from poor lubrication, and valve malfunction causing improper cycle timing. Troubleshooting involves systematic leak detection, filter inspection, and testing of control electronics. In Kenyan hospitals, power fluctuations can affect compressor operation, necessitating installation of voltage stabilizers or uninterruptible power supplies (UPS) to maintain continuous oxygen generation.

2.1.2 Cryogenic Air Separation

Cryogenic air separation is the industrial-scale process used to produce high-purity oxygen and other gases by liquefying air and distilling its components based on boiling points. This method supplies bulk oxygen to large hospitals and medical facilities.

Fundamentals of Cryogenic Air Separation

This process cools atmospheric air to temperatures below -183°C to liquefy it, then separates oxygen, nitrogen, and argon by fractional distillation in a distillation column. Because oxygen has a higher boiling point than nitrogen, it condenses first and is collected as a liquid. The liquid oxygen can then be stored in insulated cryogenic tanks for transport or onsite use.

Equipment Used in Cryogenic Plants

Key equipment includes air compressors, heat exchangers, expansion turbines, distillation columns, and insulated storage tanks. The air compressor pressurizes ambient air, which then passes through filters and coolers before entering the liquefaction unit. Distillation columns separate the components, while storage tanks maintain liquid oxygen at cryogenic temperatures.

Maintenance Considerations for Cryogenic Systems

Maintenance focuses on ensuring insulation integrity to prevent heat ingress and liquid oxygen boil-off, regular inspection of valves and seals to avoid leaks, and monitoring refrigeration systems for efficient cooling. Safety protocols for handling cryogenic liquids are mandatory, including use of personal protective equipment and proper ventilation to prevent oxygen enrichment hazards.

Advantages and Limitations of Cryogenic Production

Cryogenic air separation produces oxygen with purity >99%, suitable for critical medical applications. However, it requires significant energy input and high capital investment, making it less feasible for smaller hospitals. In Kenya, large county referral hospitals often rely on bulk supply from cryogenic plants located in industrial zones.

2.1.3 Vacuum Swing Adsorption (VSA)

Vacuum Swing Adsorption (VSA) is similar to PSA but uses vacuum rather than pressure to regenerate the adsorbent material, offering an energy-efficient alternative for oxygen generation.

Operating Principle of VSA

In VSA systems, ambient air is passed through a zeolite bed at near atmospheric pressure to adsorb nitrogen. The regeneration phase involves reducing the pressure below atmospheric by applying a vacuum to desorb nitrogen from the zeolite. This vacuum-driven cycle allows continuous oxygen production with lower energy consumption compared to PSA.

System Components and Configuration

VSA plants include blowers to supply air, vacuum pumps for regeneration, adsorption vessels, and control systems. Unlike PSA, VSA does not require high-pressure compressors, reducing mechanical complexity. Oxygen purity typically ranges between 90-93%, adequate for many clinical uses.

Maintenance and Operational Challenges

Maintaining vacuum pumps and ensuring airtight seals are critical for VSA performance. Filter maintenance prevents contamination of zeolite beds. Vacuum leaks reduce system efficiency and oxygen purity. Kenyan healthcare facilities adopting VSA technology must train technicians on vacuum system diagnostics and maintenance.

Suitability and Application Context

VSA units are suitable for medium-sized hospitals where energy efficiency and reduced maintenance costs are priorities. However, lower oxygen purity compared to cryogenic oxygen limits their use in intensive care units requiring ultra-pure oxygen. VSA technology is increasingly considered in remote or off-grid Kenyan health facilities due to lower power requirements.

2.1.4 Electrolysis of Water

Electrolysis produces oxygen and hydrogen gases by splitting water molecules using electrical energy. Though less common for medical oxygen supply, it is a potential onsite generation method in resource-limited settings.

Electrolysis Process Overview

Water molecules (H2O) are decomposed into oxygen (O2) and hydrogen (H2) gases when an electric current passes through an electrolytic cell containing water and an electrolyte. Oxygen is collected at the anode, while hydrogen is collected at the cathode. The process requires pure water and stable electrical supply.

Equipment Specifications

Name Specification Use
Electrolytic Cell Electrodes with suitable catalyst Splits water into O2 and H2
Power Supply DC power source, regulated output Provides electric current
Gas Separators Membranes or chambers Separates oxygen and hydrogen

Maintenance of Electrolytic Systems

Regular cleaning of electrodes prevents scaling and loss of efficiency. Monitoring electrolyte concentration and replacing it periodically maintains consistent gas production. Electrical connections must be inspected to avoid sparking or short circuits, which pose safety hazards in hospital environments.

Safety and Practical Considerations

Hydrogen produced is highly flammable, requiring strict ventilation and storage protocols to prevent explosions. Due to relatively low oxygen output and safety concerns, electrolysis is generally limited to small-scale or emergency oxygen supply in Kenyan rural clinics.

2.1.5 Chemical Methods

Chemical oxygen generation involves reactions that release oxygen gas from solid or liquid compounds. These methods are generally used for portable or emergency oxygen supplies rather than continuous hospital use.

Principles of Chemical Oxygen Generation

Certain chemicals, such as sodium chlorate or potassium permanganate, release oxygen when heated or reacted with water. The exothermic reactions produce oxygen gas without electrical power, making them useful in field medical kits or emergency situations.

Common Chemical Oxygen Generators

Portable chemical oxygen generators typically contain oxygen-releasing compounds in cartridges or canisters. Activation mechanisms include ignition or exposure to moisture. These devices provide oxygen for short durations, essential during power outages or transport of critical patients.

Maintenance and Handling

Chemical oxygen generators require proper storage to prevent premature activation or degradation. Expiry dates must be monitored, and damaged units replaced promptly. Training healthcare workers on safe activation and disposal is necessary to avoid chemical burns or inhalation hazards.

Advantages and Limitations in Kenyan Healthcare

Chemical oxygen generation offers a compact, power-independent solution for emergency oxygen needs in remote or disaster-prone areas. However, limited oxygen volume, single-use nature, and chemical hazards restrict their role to supplementary rather than primary oxygen supply in hospitals.

Practice Questions

  1. Explain how Pressure Swing Adsorption (PSA) technology separates oxygen from air and discuss its maintenance requirements in a hospital setting. (10 marks)

  2. Compare and contrast Cryogenic Air Separation and Vacuum Swing Adsorption (VSA) methods for oxygen production, highlighting their advantages and limitations. (12 marks)

  3. Describe the electrolysis of water process for oxygen generation and identify the safety concerns associated with its use in healthcare facilities. (8 marks)

  4. Discuss the role of chemical oxygen generation in emergency medical situations and outline precautions necessary during its use. (5 marks)

The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒2.2 Types of oxygen plants

Oxygen plants form an essential part of the medical gas infrastructure in healthcare facilities across Kenya. These plants are crucial for supplying oxygen to wards, operating theatres and emergency units, especially in county hospitals and referral centres. U…

🔒2.3 Working Mechanism of Oxygen Concentrators

Oxygen concentrators are critical devices in Kenyan healthcare facilities such as county hospitals and clinics, providing supplemental oxygen to patients with respiratory conditions. Understanding how these machines function is essential for biomedical enginee…

🔒2.4 Piping system components/parts

In biomedical engineering, the design and maintenance of medical gas piping systems in hospitals and healthcare facilities are critical for patient safety and effective clinical operations. The piping system must ensure the reliable delivery of gases such as o…

🔒2.5 Medical air applications in hospitals and healthcare facilities

Medical air is an essential utility in hospitals, used for respiratory support, anesthesia delivery, and powering pneumatic instruments. In Kenya, reliable medical air systems are integral to patient care in facilities ranging from private clinics to national…

🔒2.6 Uses and types of Gas Manifolds

In Kenyan hospitals and biomedical facilities, medical gas manifolds are essential for ensuring a continuous and reliable supply of gases such as oxygen, nitrous oxide, and medical air. These manifolds play a critical role in patient care, supporting life-savi…

Chapter Summary

This chapter explored the fundamentals of medical gas systems with a focus on oxygen production methods such as Pressure Swing Adsorption, Cryogenic Air Separation, Vacuum Swing Adsorption, Electrolysis of Water, and Chemical Methods. Different types of oxygen plants were examined, including their essential components, distribution systems, and maintenance requirements. The working principles of oxygen concentrators were detailed alongside their parts, various types, and upkeep practices. The chapter also covered the critical elements of piping systems, highlighting pipe work processes and the criteria for selecting appropriate pipes. Medical air applications within hospitals and healthcare settings were discussed, including air generation techniques and the components of medical air systems. Finally, the uses and classifications of gas manifolds were outlined, with attention to gas properties, manifold components, design considerations, installation, maintenance, and safety procedures. This comprehensive overview equips learners with the knowledge to maintain and manage medical gas systems effectively in healthcare environments.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. What is the principle behind Pressure Swing Adsorption (PSA) used in oxygen production? (2 marks)
  2. Name two advantages of cryogenic air separation for oxygen generation in hospital settings. (2 marks)
🔒20 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Explain the principle behind Pressure Swing Adsorption (PSA) technology used in oxygen production plants in Kenyan hospitals. (4 marks)
  2. Differentiate between Cryogenic Air Separation and Vacuum Swing Adsorption (VSA) in terms of oxygen purity and operational conditions. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Operate and Maintain Pressure Swing Adsorption (PSA) Oxygen Plant

Biomedical Engineering · Level 5
Hospital Plant And Building Services II
PRACTICAL ASSESSMENT
TIME: 5 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Operate the PSA oxygen plant unit and perform routine maintenance including component inspection and oxygen purity measurement as per the manufacturer's specifications for a unit producing 5 Nm3/hr oxygen.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Digital Pressure GaugeLubricating Oil (Medical Grade)
Flow MeterCleaning Cloths (Lint Free)
ManometerCleaning Solution (Isopropyl Alcohol 70%)
Set of Wrenches (8mm, 10mm, 12mm)Notebook and Pen
Screwdriver Set (Flat and Phillips)
Oxygen Purity Analyzer
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Pressure Swing Adsorption (PSA) Oxygen Plant Unit1 Unit per Candidate
2Digital Pressure Gauge1 Pc per Candidate
3Flow Meter1 Pc per Candidate
4Manometer1 Pc per Candidate
5Set of Wrenches (8mm, 10mm, 12mm)1 Set per Candidate
6Screwdriver Set (Flat and Phillips)1 Set per Candidate
7Cleaning Cloths (Lint Free)3 Pcs per Candidate
8Lubricating Oil (Medical Grade)100 ml per Candidate
9Personal Protective Equipment (PPE): Gloves, Safety Boots, Overall, Safety Goggles1 Set per Candidate
10Oxygen Purity Analyzer1 Pc per Candidate
11Cleaning Solution (Isopropyl Alcohol 70%)100 ml per Candidate
12Notebook and Pen for Recording1 Set per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: PPE and Workstation Preparation
Wore all required PPE: gloves, safety boots, overall, safety goggles
(Award 1 mark for all PPE worn as per workplace procedures)
1
Cleaned and disinfected the workstation and tools with isopropyl alcohol
(Award 1 mark for proper cleaning and disinfection)
1
Assembled all required tools and equipment before starting the task
(Award 1 mark for correct assembly of tools and equipment)
1
Sub-Total3
TASK 2: Operation of PSA Oxygen Plant
Switched on the PSA oxygen plant as per manufacturer's start-up procedure
(Award 2 marks for correct start-up procedure)
2
Monitored pressure gauges and adjusted valves to maintain correct operating pressure
(Award 3 marks for accurate pressure monitoring and adjustment)
3
Checked flow meter readings to ensure oxygen output matches 5 Nm3/hr capacity
(Award 2 marks for correct flow rate measurement and adjustment)
2
Measured oxygen purity using oxygen purity analyzer and recorded results
(Award 3 marks for correct purity measurement and documentation)
3
Checked for leaks and loose connections on all piping and fittings
(Award 2 marks for thorough leak inspection and correction)
2
Sub-Total12
TASK 3: Routine Maintenance of PSA Oxygen Plant
Inspected and cleaned air inlet filters using lint free cloth
(Award 2 marks for proper filter inspection and cleaning)
2
Lubricated moving components with medical grade oil as per manufacturer's guidelines
(Award 3 marks for correct lubrication procedure)
3
Checked and tightened all bolts and fittings using appropriate wrenches
(Award 2 marks for proper tightening and inspection)
2
Reported any abnormal noises or faults observed during operation
(Award 1 mark for proper fault reporting)
1
Cleaned the work area and stored tools after completion
(Award 1 mark for workstation cleaning and tool storage)
1
Sub-Total9
PRODUCT CHECKLIST
PSA oxygen plant operates at correct pressure (4.0 to 6.0 bar) and flow (5 Nm3/hr) as per specifications
(Award 4 marks for meeting specified pressure and flow rates)
4
Oxygen purity is within 90-95% range and recorded accurately
(Award 4 marks for correct purity level and recording)
4
All components inspected and maintained with no visible leaks or loose fittings
(Award 3 marks for proper component condition and leak-free system)
3
Workstation left clean and tools properly stored
(Award 2 marks for cleanliness and tool management)
2
Sub-Total13
GRAND TOTAL37
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Operate and Maintain Vacuum Swing Adsorption (VSA) Oxygen Plant 1500L/hr Capacity

Biomedical Engineering · Level 5
Hospital Plant And Building Services II
PRACTICAL ASSESSMENT
TIME: 5 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Operate and perform preventive maintenance on a 1500L/hr Vacuum Swing Adsorption (VSA) oxygen plant as per manufacturer’s guidelines and hospital SOP.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Digital multimeterProtective gloves
Pressure gauge testerDust coat/overall
Wrench set (metric)Safety boots/shoes
Screwdriver setSafety goggles
Vacuum gaugeCompressed air filter cartridges
Cleaning cloths (lint-free)Lubricating oil (ISO VG 32)
O-ring seals for valves
Vacuum Swing Adsorption (VSA) Oxygen Plant Manual
Writing material (notebook and pen)
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Protective gloves1 pair per Candidate
2Dust coat/overall1 piece per Candidate
3Safety boots/shoes1 pair per Candidate
4Safety goggles1 pair per Candidate
5Digital multimeter1 per Candidate
6Pressure gauge tester1 per Candidate
7Wrench set (metric)1 set per 2 Candidates
8Screwdriver set1 set per 2 Candidates
9Vacuum gauge1 per Candidate
10Compressed air filter cartridges2 pcs per Candidate
11Lubricating oil (ISO VG 32)500 ml per Candidate
12Cleaning cloths (lint-free)3 pcs per Candidate
13O-ring seals for valves5 pcs per Candidate
14Vacuum Swing Adsorption (VSA) Oxygen Plant Manual1 per Candidate
15Writing material (notebook and pen)1 set per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Safety and Preparation
Wore all required PPE: gloves, dust coat, safety boots, goggles
(Award 1 mark if all 4 PPE worn, else 0)
1
Cleaned and disinfected the work area around the VSA oxygen plant
(Award 1 mark for proper cleaning and disinfecting)
1
Assembled all required tools and materials before starting operation
(Award 1 mark for complete assembly of tools and materials)
1
Sub-Total3
TASK 2: Operating the VSA Oxygen Plant
Started the VSA oxygen plant following the correct sequence as per manual
(Award 2 marks for correct start-up procedure)
2
Monitored and recorded operating pressures at adsorption and desorption stages using pressure gauges
(Award 3 marks for accurate monitoring and recording)
3
Checked oxygen purity level using oxygen analyzer and recorded results
(Award 2 marks for correct measurement and recording)
2
Monitored vacuum levels during regeneration cycle using vacuum gauge
(Award 2 marks for correct vacuum monitoring)
2
Identified and reported any abnormal noises or vibrations during operation
(Award 1 mark for correct observation and reporting)
1
Sub-Total10
TASK 3: Preventive Maintenance Procedures
Isolated the plant from power supply safely before maintenance
(Award 1 mark for safe isolation)
1
Replaced compressed air filter cartridges correctly
(Award 2 marks for correct replacement)
2
Checked and lubricated moving parts with correct lubricating oil
(Award 2 marks for proper lubrication)
2
Inspected and replaced O-ring seals on valves where necessary
(Award 2 marks for correct inspection and replacement)
2
Tightened all accessible fittings and connections using wrench and screwdriver
(Award 2 marks for proper tightening without damage)
2
Cleaned all external surfaces and removed dust from control panel
(Award 1 mark for thorough cleaning)
1
Sub-Total10
TASK 4: Final Checks and Documentation
Restored power supply and restarted the plant safely
(Award 1 mark for safe restart)
1
Checked final operating parameters for pressure, vacuum, and oxygen purity within specified limits
(Award 3 marks for all parameters within limits)
3
Tested for any leaks using soapy water or leak detector
(Award 2 marks for leak-free system)
2
Recorded all readings, maintenance actions, and observations accurately in the plant logbook
(Award 2 marks for complete and neat documentation)
2
Cleaned and disinfected work area after completion
(Award 1 mark for proper cleaning)
1
Sub-Total9
PRODUCT CHECKLIST
Oxygen plant runs continuously with stable pressure at 4.5 bar ±0.1 bar
(Award 3 marks if pressure within specified range)
3
Oxygen purity measured at 93% minimum as per VSA plant specification
(Award 4 marks if purity ≥93%)
4
No leaks detected in piping or valves after maintenance
(Award 3 marks for zero leaks)
3
All replaced parts (filters, O-rings) installed correctly and securely
(Award 2 marks for correct installation)
2
Maintenance logbook fully and accurately completed
(Award 3 marks for complete and neat documentation)
3
Sub-Total15
GRAND TOTAL47
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Operate and Maintain Cryogenic Air Separation Oxygen PlantPractical 3
🔒Operate and Maintain an Oxygen ConcentratorPractical 4
🔒Assemble and Inspect Medical Gas Piping SystemPractical 5
🔒Install and Maintain Medical Gas Manifold System 1500mm x 800mm x 600mmPractical 6
🔒Perform safety procedures for medical gas systemsPractical 7
🔒Operate and Maintain Electrolysis Oxygen Generation SystemPractical 8
Flashcards 19 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

17 more in this section.

Create a free account
Test Yourself 20 questions Start quiz ▾
0%
0 / 2
🔒

18 more in this section.

Create a free account
Am I competent?

At the start of this chapter we promised you would be able to:

  • Follow health hazard and safety procedures correctly according to water system guidelines.
  • Inspect water system components carefully by following proper work procedures.
  • Clean water system equipment properly and safely according to work procedures.
  • Perform fault diagnosis on water system equipment accurately using the service manual.
  • Maintain and repair faulty parts of water system equipment correctly following manufacturer’s specifications.
  • Calibrate water systems precisely according to the manufacturer’s instructions.
  • Conduct a full water system functionality check following the service manual.
  • Provide clear and effective user training based on the equipment user manual.
  • Prepare detailed and accurate water systems service reports following correct work procedures.

Tick each one you can genuinely do.

So, are you there yet?

You're competent when you can confidently do 50% or more of what this chapter promised.

Sign in to record how you're doing.