Refrigeration And Air Conditioning  ·  Level 6
Electrical Installation
Chapter 2: Select correct types and sizes of cables
📚 0 Topics
⚑ What you will be able to do

By the end of this chapter, you will be able to:

  • Read and interpret electrical drawings accurately to understand job requirements.
  • Select the correct type, size, and quantity of cables and consumables needed for each job.
  • Identify and choose the right personal protective equipment (PPE) to stay safe during electrical work.
  • Select the proper PPE specifically for safe cable jointing tasks.
  • Follow IEE regulations carefully throughout all electrical installation work.
  • Perform various cable joints safely and correctly, adhering to IEE standards.
  • Accurately carry out different types of cable terminations in line with IEE regulations.
  • Properly insulate cable joints to ensure safety and compliance with IEE rules.

Mastering these skills will help you work confidently and safely, making sure every electrical installation is done right and reliable in the real world.

Electrical installation in refrigeration and air conditioning systems demands precise attention to the selection of cables, ensuring safety, efficiency, and compliance with Kenyan standards. The foundation of this process lies in accurately interpreting electrical drawings, which provide detailed guidance on the type, size, and routing of cables necessary for the installation. For refrigeration and air conditioning professionals, the ability to read and interpret these drawings is critical to avoid costly mistakes, ensure system reliability, and meet regulatory requirements in diverse settings such as hospitals, hotels, and county government offices.

1.1 Drawings are read and interpreted to determine job requirements

Electrical drawings are the blueprint for the installation process, providing comprehensive details about the electrical layout, equipment specifications, and cable routing. In the refrigeration and air conditioning sector, these drawings guide technicians on how to connect compressors, condensers, and other components safely and effectively. Mastery of reading these drawings enables professionals to plan the installation, select appropriate materials, and anticipate potential challenges on site.

1.1.1 Types of Electrical Drawings used in Refrigeration and Air Conditioning

Understanding the different types of electrical drawings is essential because each serves a unique purpose in guiding the installation process. Refrigeration and air conditioning professionals encounter various drawings that collectively ensure a seamless installation.

Layout Drawings

  • Definition: These drawings provide a top-down view of the installation site, showing positions of all equipment and major cable routes.
  • Significance: Layout drawings help technicians visualize where cables and components will be installed, facilitating efficient space use in confined mechanical rooms of hotels or hospitals.
  • Details Included: They indicate locations of compressors, control panels, and power sources.
  • Practical Use: At a county hospital, layout drawings prevent cable congestion and ensure safe pathways for maintenance access.
  • Coordination: They assist in coordinating with other trades such as plumbing and structural teams to avoid conflicts.

Wiring Diagrams

  • Definition: These focus on the connections between electrical components, showing how cables link devices.
  • Significance: Wiring diagrams clarify the exact wiring sequence and connections, critical for avoiding faults in refrigeration circuits.
  • Details Included: Cable types, terminal points, and color codes are specified.
  • Practical Use: In a SACCO office, wiring diagrams ensure that the air conditioning compressors are correctly connected to the power supply and control units.
  • Troubleshooting Aid: These diagrams are invaluable during maintenance to trace faults quickly.

Single Line Diagrams

  • Definition: Simplified representations that use single lines to denote cables and connections.
  • Significance: They provide an overview of the entire electrical system, including load distribution and protection devices.
  • Details Included: Circuit breakers, transformers, and cable sizes are shown.
  • Practical Use: At a university campus, single line diagrams help electricians understand the overall power flow to multiple air conditioning units.
  • Planning Tool: They assist in calculating load and selecting appropriate cable sizes.

Schematic Diagrams

  • Definition: These diagrams show the electrical control logic and interconnections.
  • Significance: Critical for understanding control circuits in refrigeration systems, such as thermostats and relays.
  • Details Included: Control switches, sensors, and relay coils.
  • Practical Use: In a retail business, schematic diagrams enable technicians to install and test control panels for centralized air conditioning systems.
  • Customization: They guide adjustments for system-specific control requirements.

1.1.2 Symbols and Conventions in Electrical Drawings

Interpreting electrical drawings requires familiarity with standardized symbols and conventions. This ensures clear communication among engineers, technicians, and contractors, minimizing installation errors.

Standard Symbols

  • Electrical Components: Symbols represent circuit breakers, switches, relays, and motors.
  • Cable Types: Different line styles indicate cable types such as armored or unarmored cables.
  • Connection Points: Dots and junctions show where cables connect or cross without connection.
  • Polarity and Phases: Symbols convey single-phase or three-phase power supply details.
  • Grounding: Symbols indicate earthing points essential for safety.

Colour Codes

  • Purpose: Color coding identifies cable cores, enhancing safety during installation.
  • Kenyan Standards: Brown for live, blue for neutral, and green/yellow for earth are commonly used.
  • Application: In a county government office, adherence to color codes prevents wiring errors that could lead to dangerous faults.
  • Consistency: Maintaining color standards across different sites ensures technicians can work interchangeably.
  • Documentation: Drawings specify color codes to avoid ambiguity.

Line Conventions

  • Solid Lines: Represent actual cables or conductors.
  • Dashed Lines: Indicate control wiring or future installations.
  • Arrowheads: Show direction of current flow or signal.
  • Thickness Variation: Different line thicknesses may signify cable capacity or importance.
  • Annotations: Additional notes clarify cable specifications or installation instructions.

Scale and Dimensions

  • Scale Use: Drawings are produced to scale, allowing accurate measurement of cable lengths.
  • Dimensioning: Critical distances between equipment and cable trays are marked.
  • Practical Impact: At a hospital, precise scaling ensures cables reach equipment without excessive slack or tension.
  • Verification: Technicians use scales to order correct cable lengths.
  • Adaptation: Adjustments on site are made based on scaled drawings.

1.1.3 Extracting Job Requirements from Electrical Drawings

Reading drawings with the goal of determining job requirements involves identifying the scope, materials, and procedures necessary for the installation. This skill ensures efficient project planning and resource allocation.

Equipment Identification

  • Component Listing: Drawings specify all equipment requiring electrical connection.
  • Power Ratings: Equipment ratings help in calculating cable sizes and protection devices.
  • Example: In a hotel, identifying the number and rating of air conditioning compressors guides cable selection.
  • Location Awareness: Knowing equipment placement aids cable routing decisions.
  • Integration: Coordination with HVAC design documents ensures compatibility.

Cable Type and Size Specification

  • Cable Ratings: Drawings indicate required cable types, such as armoured or flexible cables.
  • Size Determination: Based on current load and installation environment.
  • Example: A retail store’s refrigeration unit may require specific cable sizes to handle start-up currents.
  • Environmental Factors: Drawings note cable insulation requirements for wet or hot locations.
  • Standards Compliance: Specifications align with Kenyan Electrical Installations Code.

Load and Protection Details

  • Current Loads: Drawings show expected electrical loads per circuit.
  • Protection Devices: Types and ratings of fuses or circuit breakers are indicated.
  • Example: At a university, correct overload protection prevents damage to air conditioning compressors.
  • Safety Margins: Drawings incorporate safety factors for transient loads.
  • Coordination: Protection devices must match cable capacities.

Installation Instructions

  • Routing Paths: Drawings define cable trays, conduits, and entry points.
  • Fixing Methods: Notes on securing cables to avoid mechanical damage.
  • Example: In a county hospital, routing cables away from water pipes reduces risk of short circuits.
  • Compliance: Instructions ensure adherence to occupational safety standards.
  • Testing Requirements: Drawings may specify post-installation tests.

1.1.4 Common Challenges in Interpreting Electrical Drawings and Solutions

Despite their importance, electrical drawings can present challenges to refrigeration and air conditioning professionals. Recognizing these difficulties and knowing how to overcome them is vital for successful installations.

Complexity and Detail Overload

  • Challenge: Detailed drawings with numerous components can overwhelm technicians.
  • Solution: Breaking down drawings into sections focusing on relevant parts simplifies interpretation.
  • Example: In a SACCO office, focusing first on power circuits before control wiring clarifies tasks.
  • Use of Highlighting: Marking key components on printed drawings aids focus.
  • Consultation: Engaging design engineers for clarification reduces errors.

Inconsistent or Outdated Drawings

  • Challenge: Drawings may not reflect recent design changes.
  • Solution: Cross-checking with site engineers and updated documentation ensures accuracy.
  • Practice: At a retail business, verifying drawings before cable procurement prevents waste.
  • Version Control: Ensuring the latest revision is used avoids confusion.
  • Field Adjustments: Documenting on-site changes maintains record integrity.

Symbol Misinterpretation

  • Challenge: Misreading symbols leads to incorrect connections.
  • Solution: Training on standard symbols and use of legend keys on drawings is essential.
  • Example: In a county government office, correct symbol interpretation ensures proper earthing.
  • Reference Materials: Keeping standard symbol guides accessible on site supports accuracy.
  • Peer Review: Double-checking drawings with colleagues reduces mistakes.

Scale and Dimension Errors

  • Challenge: Misjudging scale can result in incorrect cable lengths.
  • Solution: Using measuring tools and verifying scales before ordering materials prevents shortages.
  • Site Practice: At a university, technicians measure actual distances to confirm drawing accuracy.
  • Digital Tools: Utilizing software to interpret scaled drawings enhances precision.
  • Contingency Planning: Ordering slightly longer cables accommodates minor discrepancies.

Communication Gaps

  • Challenge: Poor communication between designers and installers can cause misunderstandings.
  • Solution: Regular coordination meetings and clear documentation improve information flow.
  • Example: In a hospital installation, weekly progress reviews help resolve design queries promptly.
  • Feedback Loops: Reporting site findings back to designers refines future drawings.
  • Training Workshops: Joint sessions between engineers and technicians build mutual understanding.

Practice Questions

  1. Explain the role of layout drawings in the installation of refrigeration and air conditioning electrical systems. (5 marks)
  2. Describe five standard symbols commonly found in electrical drawings and their significance in refrigeration installations. (10 marks)
  3. Outline six steps you would take to extract job requirements from electrical drawings for a new air conditioning installation in a county government office. (12 marks)
  4. Identify four common challenges faced when interpreting electrical drawings and propose solutions for each within the context of refrigeration and air conditioning projects. (12 marks)

Correct Type, Size and Quantity of Cables and Related Consumables

In refrigeration and air conditioning (RAC) electrical installations across Kenya, selecting the correct cables and consumables is crucial. The choice directly impacts system safety, efficiency, and longevity, especially in environments such as hospitals, universities, or commercial buildings where these systems operate continuously. A well-chosen cable prevents overheating, voltage drops, and potential fire hazards, while the correct quantity of consumables ensures smooth installation and future maintenance.

1.1.1 Correct Type of Cables for RAC Electrical Installations

The type of cable selected for refrigeration and air conditioning systems must suit the electrical load, environmental conditions, and regulatory standards. Different cable types offer varying levels of insulation, flexibility, and durability, which affect their suitability for specific RAC components such as compressors, fans, and control panels.

Characteristics of Suitable Cable Types for RAC

  • Thermoplastic Insulated Cables (PVC cables): Commonly used for indoor wiring, these cables have insulation resistant to heat and moisture. In offices with air conditioning units, PVC cables provide a reliable and cost-effective solution.
  • Thermoset Insulated Cables (XLPE cables): These cables withstand higher temperatures and are more resistant to chemical exposure. They are preferred in industrial refrigeration plants where ambient temperatures can vary widely.
  • Armoured Cables (Steel Wire Armoured - SWA): Used in outdoor or underground installations, SWA cables protect conductors from mechanical damage. For example, in county government offices with external AC units, SWA cables ensure durability and protection.
  • Flexible Cables: Used for connections requiring movement, such as between compressor motors and control panels. These cables accommodate vibration and reduce stress on connections in refrigeration units.
  • Fire-Resistant Cables: In hospitals or hotels, fire-resistant cables maintain circuit integrity during a fire, allowing critical RAC systems to continue operating for safety and comfort.

1.1.2 Correct Size of Cables for RAC Electrical Installations

Cable size selection depends on current-carrying capacity, voltage drop, and short-circuit withstand capability. Undersized cables overheat and cause energy losses, while oversized cables increase costs unnecessarily.

Factors Influencing Cable Size Selection

  • Load Current: The cable must handle the maximum current drawn by RAC equipment without overheating. For instance, a commercial refrigeration unit in a supermarket draws significant current requiring a cable sized to handle peak loads.
  • Voltage Drop: Excessive voltage drop reduces equipment performance and lifespan. Kenyan standards recommend voltage drop not exceeding 5% for RAC circuits to maintain compressor efficiency.
  • Ambient Temperature: High ambient temperatures, such as in Nairobi’s industrial zones, require derating cable current capacity, leading to larger cable sizes.
  • Installation Method: Cables installed in conduit, underground, or in free air have different heat dissipation characteristics affecting size selection.
  • Short-Circuit Withstand: The cable must withstand fault currents long enough for protective devices to operate without damage.

1.1.3 Quantity of Cables and Related Consumables

Estimating the correct quantity of cables and consumables ensures project continuity and cost efficiency. Consumables include cable lugs, connectors, insulation tapes, conduits, clips, and glands necessary for secure and compliant installations.

Key Considerations in Quantity Estimation

  • Circuit Length: Accurate measurement of cable runs from power sources to RAC equipment determines cable length needed.
  • Spare Lengths: Providing 5-10% additional cable length accommodates routing changes and future repairs.
  • Number of Circuits: Multiple RAC units or multi-stage systems require separate cable runs, increasing total cable quantity.
  • Consumables per Cable Run: Each cable run requires connectors, lugs, and protective sleeves proportional to the number of cable ends and joints.
  • Project Complexity: Complex installations such as at university laboratories require more joints and protective devices, increasing consumables.

1.1.4 Related Consumables for RAC Electrical Installations

Consumables complement cables by facilitating safe terminations, mechanical protection, and environmental sealing. Their quality and compatibility with cables influence installation reliability.

Common Consumables and Their Roles

  • Cable Lugs and Connectors: Provide secure electrical connections between cables and equipment terminals. For example, in a county hospital’s cold storage unit, corrosion-resistant lugs prevent power interruptions.
  • Cable Glands: Seal cable entry points to control panels, preventing dust and moisture ingress, critical in humid environments such as coastal hotels.
  • Insulation Tapes: Used to insulate joints and repairs, ensuring electrical safety and continuity.
  • Conduits and Trunking: Protect cables from mechanical damage and facilitate neat installation in commercial buildings.
  • Cable Clips and Ties: Secure cables along routes to prevent sagging and physical damage, essential in installations at retail outlets with exposed wiring routes.

Practice Questions

  1. Explain why the selection of the correct cable type is critical in refrigeration and air conditioning electrical installations. (10 marks)
  2. List and explain five factors that influence the correct sizing of cables in RAC systems. (15 marks)
  3. Describe how you would estimate the quantity of cables and consumables for installing an air conditioning system in a university laboratory. (10 marks)
  4. Identify five essential consumables used in RAC cable installations and explain their functions. (15 marks)
The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒1.1 Correct PPE Are Identified and Selected in Line with Safety

In refrigeration and air conditioning electrical installations, the correct use of Personal Protective Equipment (PPE) is critical to ensure technician safety. Kenya’s work environments often present hazards such as electrical shocks, burns, and exposure to re…

Chapter Summary

This chapter focused on the essential skills required to select the correct types and sizes of cables for electrical installations. It began by emphasizing the importance of accurately reading and interpreting technical drawings to determine the specific requirements of the job. Understanding these drawings enables the installer to identify the correct cable specifications needed for safe and efficient operation. The chapter then covered the process of selecting the appropriate types, sizes, and quantities of cables along with the necessary related consumables to ensure a complete and compliant installation. Additionally, it highlighted the significance of identifying and choosing the correct personal protective equipment to maintain safety standards during installation work. The integration of technical knowledge with practical safety considerations prepares students to approach electrical installation tasks with confidence and professionalism.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. What is the primary purpose of reading and interpreting electrical drawings in refrigeration and air conditioning installations? (2 marks)
  2. Identify three types of cables commonly used in refrigeration and air conditioning electrical installations. (3 marks)
🔒28 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Explain how electrical drawings are used to determine the type and quantity of cables required for an air conditioning installation at a Nairobi hospital. (4 marks)
  2. Identify four common types of cables used in refrigeration and air conditioning electrical installations and state one key characteristic of each. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Identify and Sort Electrical Cable Types for Various Installations

Refrigeration And Air Conditioning · Level 6
Electrical Installation
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Identify and sort five types of electrical cables by type and application, tagging each cable correctly with its size and typical use.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Electrical Cable CutterTwin and Earth Cable 2.5mm²
Wire StrippersArmoured Steel Wire Cable 10mm²
Insulated Screwdriver SetFlexible PVC Cable 1.5mm²
Digital MultimeterCoaxial Cable RG6
Permanent MarkerCable Identification Tags
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Twin and Earth Cable 2.5mm²1 roll per 5 Candidates
2Armoured Steel Wire Cable 10mm²1 length per 5 Candidates
3Flexible PVC Cable 1.5mm²1 roll per 5 Candidates
4Coaxial Cable RG61 length per 10 Candidates
5Electrical Cable Cutter1 per Candidate
6Wire Strippers1 per Candidate
7Insulated Screwdriver Set1 set per Candidate
8Digital Multimeter1 per Candidate
9Cable Identification Tags10 pcs per Candidate
10Permanent Marker1 per Candidate
11Electrical Gloves1 pair per Candidate
12Safety Boots1 pair per Candidate
13Dust Coat/Overall1 per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Safety and Preparation
Wore PPE including gloves, dust coat, and safety boots
(Award 1 mark for complete correct PPE use or zero)
1
Handled tools and equipment as per workshop safety procedures
(Award 1 mark for correct and safe use or zero)
1
Sub-Total2
TASK 2: Cable Identification and Sorting
Selected each cable type from the assortment
(Award 1 mark for correct selection or zero)
1
Measured and verified cable sizes using wire strippers or multimeter
(Award 1 mark for accurate measurement or zero)
1
Identified and explained typical applications for each cable type
(Award up to 2 marks for correct identification and explanation or zero)
2
Tagged each cable correctly with size and application using cable tags and permanent marker
(Award up to 2 marks for accurate and neat tagging or zero)
2
Sub-Total6
TASK 3: Final Inspection and Housekeeping
Ensured all cables were correctly sorted and tagged
(Award 1 mark for complete and correct sorting or zero)
1
Cleaned and stored tools and equipment properly
(Award 1 mark for proper housekeeping or zero)
1
Disposed of any waste materials as per workshop policy
(Award 1 mark for correct disposal or zero)
1
Sub-Total3
PRODUCT CHECKLIST
All five cable types correctly identified and tagged with accurate size and application
(Award 1 mark per correctly identified and tagged cable or zero)
5
Tags are legible, neat, and firmly attached
(Award 2 marks for neat and permanent tagging or zero)
2
Sub-Total7
GRAND TOTAL18
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Measure and determine cable sizes for lighting circuits

Refrigeration And Air Conditioning · Level 6
Electrical Installation
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Measure and determine the correct cable sizes for a lighting circuit supplying 10 light points with a total load of 1200W over a 30m run.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Measuring tape (5m)Cable size chart (printed)
Digital multimeterLighting load specification sheet
CalculatorElectrical gloves
Insulated screwdriver setSafety boots
PliersDust coat/overall
Wire strippers and cuttersNotebook and pen
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Measuring tape (5m)1 Pc per Candidate
2Digital multimeter1 Pc per Candidate
3Cable size chart (printed)1 Pc per Candidate
4Calculator1 Pc per Candidate
5Insulated screwdriver set1 Set per Candidate
6Pliers1 Pc per Candidate
7Wire strippers and cutters1 Pc per Candidate
8Electrical gloves1 Pair per Candidate
9Safety boots1 Pair per Candidate
10Dust coat/overall1 Pc per Candidate
11Notebook and pen1 Set per Candidate
12Lighting load specification sheet1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Preparation and Safety
Wore PPE as per SOPs (gloves, dust coat/overall, safety boots)
(Award 1 mark for correct PPE use or zero)
1
Handled tools and equipment as per workshop procedure
(Award 1 mark for correct and safe tool handling or zero)
1
Sub-Total2
TASK 2: Measurement and Calculation
Measured the length of the lighting circuit accurately using measuring tape
(Award 2 marks for accurate measurement or zero)
2
Checked and recorded the total lighting load from the specification sheet
(Award 1 mark for correct load identification or zero)
1
Used the cable size chart and calculations to determine the correct cable size
(Award up to 3 marks for correct calculation and cable size selection or zero)
3
Recorded all measurements and calculations clearly in the notebook
(Award 1 mark for clear and complete recording or zero)
1
Sub-Total7
TASK 3: Final Reporting and Housekeeping
Prepared a clear report listing the cable size selected, load details, and length of circuit
(Award 2 marks for clear and complete report or zero)
2
Performed housekeeping by cleaning the workstation and storing tools properly
(Award 1 mark for proper housekeeping or zero)
1
Sub-Total3
PRODUCT CHECKLIST
Cable size selection matches calculated load and circuit length (e.g. 1.5mm² or 2.5mm² as appropriate)
(Award 3 marks for correct cable size selection or zero)
3
Measurement accuracy within ±0.1m of actual circuit length
(Award 2 marks for accurate measurement or zero)
2
Written report is clear, complete, and professional
(Award 2 marks for quality of report or zero)
2
Sub-Total7
GRAND TOTAL19
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Measure and determine cable sizes for power distribution circuitsPractical 3
🔒Select Suitable Cables for Underground Electrical InstallationPractical 4
🔒Select suitable cables for a 100m overhead electrical installationPractical 5
🔒Determine Cable Sizes for a 230V Lighting Circuit Considering Voltage DropPractical 6
🔒Determine correct cable sizes based on current carrying capacity for specified installation conditionsPractical 7
🔒Select fire-resistant cables for a fire alarm system installationPractical 8
🔒Prepare Cable Schedule and Selection Chart for a Residential Electrical InstallationPractical 9
🔒Select Appropriate Cable Types and Sizes from Installation DrawingsPractical 10
Flashcards 20 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

18 more in this section.

Create a free account
Test Yourself 19 questions Start quiz ▾
0%
0 / 2
🔒

17 more in this section.

Create a free account
Am I competent?

At the start of this chapter we promised you would be able to:

  • Read and interpret electrical drawings accurately to understand job requirements.
  • Select the correct type, size, and quantity of cables and consumables needed for each job.
  • Identify and choose the right personal protective equipment (PPE) to stay safe during electrical work.
  • Select the proper PPE specifically for safe cable jointing tasks.
  • Follow IEE regulations carefully throughout all electrical installation work.
  • Perform various cable joints safely and correctly, adhering to IEE standards.
  • Accurately carry out different types of cable terminations in line with IEE regulations.
  • Properly insulate cable joints to ensure safety and compliance with IEE rules.

Tick each one you can genuinely do.

So, are you there yet?

You're competent when you can confidently do 50% or more of what this chapter promised.

Sign in to record how you're doing.