Refrigeration And Air Conditioning  ·  Level 6
Air Conditioning Units Installation
Chapter 7: Conduct site survey
📚 7 Topics

Conducting a thorough site survey is essential before installing air conditioning units to ensure optimal system performance and longevity. In Kenya’s diverse climatic zones, ranging from the hot coastal regions to cooler highlands, understanding the site-specific conditions influences the choice of equipment and installation techniques. Among the critical activities during a site survey is conducting leakage tests, an indispensable procedure to maintain system efficiency, safety, and compliance with environmental standards. This chapter explores the methodologies and best practices for conducting leakage tests in refrigeration and air conditioning installations within the Kenyan professional context.

7.1 Conducting Leakage Tests

Leakage testing is a vital step in the installation and maintenance of air conditioning systems, designed to detect and prevent refrigerant loss. Given the cost of refrigerants and their environmental impact, especially with strict regulations enforced by the National Environment Management Authority (NEMA) in Kenya, leakage control is a priority for technicians. Proper leakage testing safeguards system performance, reduces operational costs, and minimizes harmful emissions.

7.1.1 Purpose and Importance of Leakage Tests

Leakage tests serve multiple critical functions in the lifecycle of air conditioning units. Understanding these purposes provides clarity on why rigorous testing is non-negotiable in professional practice.

Purpose of Leakage Tests

  • Detecting Refrigerant Loss: Leakage tests identify points where refrigerant escapes, preventing system inefficiency and ensuring the unit operates at designed capacity.
  • Ensuring System Safety: Leaks can lead to harmful refrigerant exposure or create flammable atmospheres, especially with hydrocarbon refrigerants, posing safety risks to occupants and technicians.
  • Preventing Environmental Damage: Refrigerants such as HFCs contribute to global warming; detecting leaks aligns with Kenya’s commitment to environmental protection under international protocols.
  • Complying with Regulations: NEMA requires regular leak inspections to minimize environmental impact and enforce responsible refrigerant handling.
  • Maintaining Equipment Longevity: Early leak detection prevents compressor damage caused by low refrigerant levels, thereby extending equipment life.

Importance of Leakage Tests

  • Cost Savings: Avoiding refrigerant loss reduces the need for frequent recharging, lowering operational expenses for commercial facilities like hotels or county government offices.
  • System Efficiency: Leaks reduce pressure and cooling capacity, leading to higher energy consumption and utility bills in institutions such as hospitals or banks.
  • Health and Safety Compliance: Preventing leaks protects workers and occupants from exposure to toxic or flammable gases.
  • Enhancing Reputation: Service providers who consistently perform leak tests demonstrate professionalism and compliance, enhancing trust with clients.
  • Supporting Sustainable Practices: Leak management contributes to Kenya’s national goals for sustainable development and climate action.

7.1.2 Types of Leakage Tests Used in Air Conditioning Installation

Various leakage testing methods are applied depending on the system type, refrigerant used, and site conditions. Kenyan refrigeration professionals should be proficient in selecting and applying the appropriate technique for effective leak detection.

Pressure Testing

  • This method involves pressurizing the system with dry nitrogen or air to a specified level and monitoring pressure drop over time. It is suitable for new installations and repair work.
  • Pressure testing is preferred for detecting large leaks quickly, especially in sealed systems before refrigerant charging.
  • Dry nitrogen is favored to avoid moisture contamination and oxidation inside the system.
  • The test pressure must comply with manufacturer specifications to avoid damaging components.
  • Pressure decay indicates the presence of leaks, requiring pinpointing and repair.

Electronic Leak Detection

  • Electronic leak detectors use sensors to detect refrigerant gases in the air, offering high sensitivity for pinpointing small leaks.
  • This method is effective for both installed and operating systems and can detect leaks invisible to the naked eye.
  • Instruments must be calibrated regularly for accuracy, especially when used in environments with background gases.
  • Electronic detectors are commonly used in hotels and commercial buildings for routine maintenance checks.
  • They can differentiate between different refrigerants, aiding in precise diagnostics.

Soap Bubble Testing

  • Soap bubble testing is a simple, low-cost method involving applying a soapy solution on joints and observing bubble formation at leak points.
  • It is most effective for accessible fittings, valves, and connections during installation or maintenance.
  • This method is limited by its subjective nature and inability to detect very small leaks.
  • Soap bubble testing complements other methods by providing a quick visual check.
  • It is widely used in small-scale installations and training scenarios.

Ultrasonic Leak Detection

  • Ultrasonic detectors identify high-frequency sound waves produced by escaping gases, useful in noisy industrial environments.
  • This technique is non-invasive and can locate leaks behind panels or in concealed areas.
  • Ultrasonic testing is valuable in large commercial complexes such as universities or hospitals, where system complexity is high.
  • The equipment requires skilled operators to distinguish leak sounds from ambient noise.
  • It is particularly suited for halogenated refrigerants.

7.1.3 Equipment and Tools for Leakage Testing

Accurate leakage detection depends on using appropriate tools and maintaining them properly. Kenyan refrigeration technicians must be familiar with specifications and operational protocols for these instruments.

Name Specification Use
Electronic Leak Detector Sensitivity: 1g/year or less; Rechargeable battery Detects refrigerant gas leaks in air
Dry Nitrogen Cylinder Purity: 99.99%; Pressure: 200 bar Pressurizes system for pressure testing
Soap Solution Spray Soapy water with surfactant Visual detection of leaks via bubbles
Ultrasonic Leak Detector Frequency range: 20kHz – 100kHz; Portable Detects ultrasonic sound from leaks
Pressure Gauge Range: 0-600 psi; Accuracy: ±1% Measures system pressure during tests
  • Electronic detectors require calibration every six months to ensure sensitivity.
  • Nitrogen cylinders must be handled with care to avoid accidents and stored in well-ventilated areas.
  • Soap solutions should be freshly prepared to maintain bubble formation effectiveness.
  • Ultrasonic detectors need regular battery charging and operator training for reliable results.
  • Pressure gauges must be checked for leaks and zeroed before use.

7.1.4 Procedures for Conducting Leakage Tests

Performing leakage tests involves a systematic approach to ensure thorough inspection and accurate results. The following steps outline a standard procedure suitable for air conditioning installations in Kenyan commercial and institutional sites.

  1. Prepare the System: Isolate the air conditioning system by closing service valves and ensure it is depressurized and free of refrigerant where applicable.
  2. Choose Testing Method: Select the appropriate leak test method based on system status, refrigerant type, and site conditions.
  3. Pressurize the System: Using dry nitrogen, pressurize the system to the manufacturer’s recommended test pressure, typically around 150-200 psi.
  4. Monitor Pressure: Observe the pressure gauge for a specified period, usually 15-30 minutes, noting any pressure drop that indicates leaks.
  5. Detect Leak Points: Use electronic or ultrasonic detectors to scan joints, fittings, and components for escaping refrigerant.
  6. Apply Soap Solution: Spray soap solution on suspected leak points and watch for bubble formation confirming leaks.
  7. Document Findings: Record all detected leaks, their locations, and severity for repair planning and regulatory compliance.
  8. Repair and Retest: Repair identified leaks using approved materials and methods, then repeat the testing process to confirm leak elimination.
  9. Evacuate and Recharge: Once leak-free status is confirmed, evacuate the system to remove air and moisture before recharging with the correct refrigerant.
  10. Final Inspection: Conduct a final leak test after commissioning to ensure system integrity.

Practice Questions

  1. Explain the environmental and economic reasons why leakage tests are crucial in air conditioning installations in Kenya. (8 marks)
  2. Describe four different methods used for detecting leaks in refrigeration systems and explain the suitability of each method. (12 marks)
  3. Outline the step-by-step procedure for conducting a pressure leakage test on an air conditioning system. (10 marks)
  4. Identify and explain five key pieces of equipment used in leakage testing and their maintenance requirements. (10 marks)
The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒7.2 Testing of Temperature Settings

In refrigeration and air conditioning installations, verifying the accuracy and appropriateness of temperature settings is a critical step during commissioning and routine maintenance. In Kenya’s diverse climate zones, from coastal humidity to Nairobi’s cooler…

🔒7.3 Measurement of Current and Voltage

The accurate measurement of electrical current and voltage is fundamental for refrigeration and air conditioning professionals in Kenya during site surveys and installations. Understanding these electrical parameters ensures systems operate within manufacturer…

🔒7.4 Sound and vibration checking

In refrigeration and air conditioning installations, assessing sound and vibration levels during site surveys is critical to guarantee system performance and user comfort. In Kenya, where installations often occur in sensitive environments such as hospitals, h…

🔒7.5 Checking the Operation of Air Conditioning System Within Acceptable Standards

Ensuring that an air conditioning system operates within acceptable standards is critical for performance, energy efficiency, and occupant comfort in Kenyan commercial and institutional buildings. After installation, technicians must verify that the system mee…

🔒7.6 Commissioning and handing over procedures

In the Kenyan refrigeration and air conditioning industry, commissioning and handing over mark the critical transition from installation to operational use. Effective commissioning ensures that air conditioning units perform according to design specifications…

🔒7.7 Report Writing

Report writing is a critical skill for refrigeration and air conditioning professionals in Kenya, particularly during and after conducting site surveys. A well-structured report communicates findings clearly, supports decision-making, and facilitates project p…

Chapter Summary

This chapter covered essential procedures for ensuring the proper installation and functioning of air conditioning units, starting with conducting leakage tests to identify and address any refrigerant escapes that could impair system efficiency. It then discussed the importance of testing temperature settings to verify that the system maintains desired environmental conditions accurately. The measurement of current and voltage was explained as a critical step to confirm electrical parameters are within safe and optimal limits. Sound and vibration checking were highlighted to detect any mechanical issues that might affect performance or cause discomfort. The chapter also detailed how to assess the operation of the air conditioning system against acceptable standards to ensure compliance and reliability. Commissioning and handing over procedures were described as vital for formally concluding installation and transferring responsibility to the client. Finally, the chapter emphasized the role of thorough report writing to document all findings, tests, and actions taken during the installation process.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. What is the primary purpose of conducting a leakage test on an air conditioning unit? (2 marks)
  2. Describe the procedure for testing temperature settings in an air conditioning system. (3 marks)
🔒20 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Describe the steps involved in conducting a leakage test on a split air conditioning unit installed at a Nairobi hotel. (4 marks)
  2. Explain the importance of verifying temperature settings during the commissioning of an air conditioning system in a county government office. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Perform Leakage Test on Air Conditioning Unit

Refrigeration And Air Conditioning · Level 6
Air Conditioning Units Installation
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Perform a leakage test on a split air conditioning unit including pressurization with nitrogen and leak detection as per standard procedures.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Manifold Gauge Set with Charging HosesSplit Air Conditioning Unit
Leak DetectorOxygen Free Dry Nitrogen (OFDN) Cylinder
Vacuum PumpCopper Tubes 1/2 inch Diameter
Flaring KitSealants
Assorted PliersEmery Cloth
Assorted Screwdrivers
Allen Key Set
Tape Measure
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Split Air Conditioning Unit1 Pc per Candidate
2Oxygen Free Dry Nitrogen (OFDN) Cylinder1 Cylinder per 3 Candidates
3Manifold Gauge Set with Charging Hoses1 Set per Candidate
4Leak Detector (Electronic or Soap Foam)1 Pc per Candidate
5Vacuum Pump1 Pc per 3 Candidates
6Flaring Kit1 Kit per Candidate
7Copper Tubes 1/2 inch Diameter2 meters per Candidate
8Assorted Pliers1 Pc per Candidate
9Assorted Screwdrivers1 Set per Candidate
10Allen Key Set1 Set per Candidate
11Safety Overall1 Pc per Candidate
12Safety Boots1 Pair per Candidate
13Safety Gloves1 Pair per Candidate
14Safety Goggles1 Pc per Candidate
15Sealants (Silicone or equivalent)Enough per Candidate
16Emery ClothEnough per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Conduct Leakage Test on Air Conditioning Unit
Wore appropriate PPE including safety overall, gloves, boots, and goggles
(Award 1 mark for wearing all PPE correctly or zero)
1
Selected and handled tools and equipment correctly as per workshop procedure
(Award 1 mark for correct tool selection and 1 mark for safe handling)
2
Connected manifold gauge set and OFDN cylinder correctly to the system
(Award 1 mark for correct connection of manifold gauge, 1 mark for nitrogen cylinder connection)
2
Pressurized the system to 450 kPa using OFDN and maintained pressure for 10 minutes
(Award 1 mark for setting correct pressure, 1 mark for maintaining pressure, 1 mark for monitoring gauges)
3
Checked for leaks using electronic leak detector or soap foam on all joints and connections
(Award 1 mark for thorough inspection, 1 mark for correct use of detector, 1 mark for identifying leaks if any)
3
Took corrective action on any detected leaks including tightening and resealing
(Award 2 marks if all leaks were correctly addressed or zero)
2
Performed vacuum pump evacuation after leak test
(Award 1 mark for correct connection, 1 mark for achieving vacuum to zero gauge reading)
2
Performed housekeeping by cleaning work area, tools and disposing of waste properly
(Award 1 mark for complete housekeeping or zero)
1
Sub-Total16
PRODUCT CHECKLIST
System pressurized to 450 kPa and held pressure without drop for 10 minutes
(Award 3 marks for stable pressure with no leaks detected)
3
All joints and connections sealed properly with no visible leaks
(Award 3 marks for leak-free joints and proper sealing)
3
Vacuum evacuation achieved to zero gauge reading indicating no contamination
(Award 2 marks for complete evacuation to zero pressure)
2
Leak test report prepared including tools used, procedure followed, and results recorded
(Award 2 marks for clear, complete, and accurate report)
2
System physically intact and operational after test with no damage
(Award 2 marks for no damage and correct reassembly)
2
Sub-Total12
GRAND TOTAL28
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Test and Adjust Temperature Settings of a Split Air Conditioning Unit

Refrigeration And Air Conditioning · Level 6
Air Conditioning Units Installation
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Test and adjust the temperature settings of a split air conditioning unit to achieve an indoor temperature of 22°C ± 1°C as per manufacturer's specifications.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Digital Thermometer/Temperature ProbeSplit Air Conditioning Unit
Manifold Gauge with Charging HoseSafety Gloves
Digital MultimeterSafety Goggles
Insulated Screwdriver SetSafety Overall
PliersSafety Boots
Allen Keys Set
Electrical Tape
Leak Detector
Vacuum Pump
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Split Air Conditioning Unit1 Pc per Candidate
2Digital Thermometer/Temperature Probe1 Pc per Candidate
3Manifold Gauge with Charging Hose1 Set per Candidate
4Digital Multimeter1 Pc per Candidate
5Insulated Screwdriver Set1 Set per Candidate
6Pliers1 Pc per Candidate
7Allen Keys Set1 Set per Candidate
8Electrical Tape1 Roll per Candidate
9Leak Detector1 Pc per Candidate
10Vacuum Pump1 Pc per Candidate
11Safety Gloves1 Pair per Candidate
12Safety Goggles1 Pc per Candidate
13Safety Overall1 Pc per Candidate
14Safety Boots1 Pair per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Prepare for Temperature Testing and Adjustment
Wore appropriate PPE: Safety gloves, goggles, overall, and boots
(Award 1 mark for wearing all required PPE)
1
Selected correct tools and equipment as per job specification
(Award 1 mark for correct selection and readiness)
1
Verified power supply and ensured unit is safely energized
(Award 1 mark for correct power verification and safety)
1
Checked unit for visible damage or leaks using leak detector
(Award 1 mark for thorough inspection and leak check)
1
Set up digital thermometer and manifold gauge correctly
(Award 1 mark for correct setup and connection)
1
Measured initial indoor unit temperature and system pressures
(Award 1 mark for accurate measurement and recording)
1
Identified deviations from specified temperature range
(Award 1 mark for correct identification of temperature deviation)
1
Sub-Total7
TASK 2: Adjust Temperature Settings and Confirm Operation
Adjusted thermostat settings to target 22°C ± 1°C
(Award 1 mark for correct adjustment of thermostat)
1
Adjusted refrigerant charge if necessary using manifold gauge
(Award 2 marks for correct charging and pressure adjustment)
2
Monitored temperature and pressure during operation for stability
(Award 1 mark for continuous monitoring and recording)
1
Checked for unusual noises or vibrations during operation
(Award 1 mark for inspection and identification of operational faults)
1
Tested remote control and unit response
(Award 1 mark for functional remote control test)
1
Performed housekeeping: cleaned work area and stored tools properly
(Award 1 mark for proper housekeeping after task completion)
1
Sub-Total7
TASK 3: Prepare Service Report
Prepared a detailed service report including title and date
(Award 1 mark for complete report heading)
1
Listed all tools and equipment used during the task
(Award 1 mark for accurate listing)
1
Described procedure followed for testing and adjustment
(Award 1 mark for clear procedural description)
1
Recorded final temperature and pressure readings
(Award 1 mark for accurate and complete recording)
1
Noted any faults found and corrective actions taken
(Award 1 mark for detailed fault and correction notes)
1
Sub-Total5
PRODUCT CHECKLIST
Temperature setting adjusted to 22°C ± 1°C within 15 minutes
(Award 2 marks for meeting specified temperature range promptly)
2
System pressures within manufacturer’s recommended range
(Award 2 marks for correct pressure adjustment)
2
No refrigerant leaks detected after adjustment
(Award 1 mark for leak-free system)
1
Service report is complete, accurate, and legible
(Award 2 marks for professional and complete report)
2
Sub-Total7
GRAND TOTAL26
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Measure Electrical Current and Voltage of an Air Conditioning UnitPractical 3
🔒Check sound and vibration levels of an installed air conditioning systemPractical 4
🔒Verify Operation of Split Air Conditioning Unit Within Acceptable StandardsPractical 5
🔒Commission and Hand Over a Split Air Conditioning UnitPractical 6
🔒Prepare site survey and testing report for split air conditioning unit installationPractical 7
🔒Integrated Electrical and Leakage Testing of Air Conditioning UnitPractical 8
🔒Integrated Temperature and Operational Performance Testing of a Split Air Conditioning UnitPractical 9
🔒Sound and Vibration Assessment with Report Preparation for Air Conditioning Installation SitePractical 10
Flashcards 20 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

18 more in this section.

Create a free account
Test Yourself 17 questions Start quiz ▾
0%
0 / 2
🔒

15 more in this section.

Create a free account