Refrigeration And Air Conditioning  ·  Level 5
Electrical Motor Control Principles
Chapter 8: Apply extended-delta reduced-voltage starter circuits
📚 4 Topics
⚑ What you will be able to do

By the end of this chapter, you will be able to:

  • Apply the principles and methods of extended-delta reduced-voltage starter circuits for delta reduced three-phase asynchronous motors based on job voltage starter requirements.
  • Correctly connect extended-delta reduced-voltage starter circuits for three-phase asynchronous motors following ASHRAE and IEE standards.
  • Debug extended-delta reduced-voltage starter circuits accurately to ensure proper motor operation.
  • Diagnose issues in extended-delta reduced-voltage starter circuits according to job requirements with confidence.
  • Prepare detailed and clear diagnosis reports following workplace procedures.

Mastering these skills will help you ensure motors start safely and efficiently, making you a valuable technician in the electrical motor control trade.

Extended-delta reduced-voltage starter circuits are fundamental in controlling the starting current and torque of three-phase asynchronous motors, widely used in Kenyan industries such as manufacturing plants, hospital power backup systems, and agricultural processing units. These circuits allow motors to start with a lower voltage, reducing mechanical stress and electrical demand on the supply network, which is essential in environments with limited power capacity or sensitive equipment. Understanding the principles and methods of these starter circuits enables technicians and engineers to design and maintain reliable motor control systems that enhance operational efficiency and equipment longevity.

8.1 Principle and the method of extended-delta reduced-voltage starter circuits of three-phase asynchronous motor

The extended-delta reduced-voltage starter is an advanced motor starting method designed to minimize the inrush current during motor startup while providing sufficient starting torque. This is particularly important in Kenyan industrial settings such as county referral hospitals where electrical loads must be managed carefully to avoid tripping main supply breakers or causing voltage dips that could affect sensitive medical equipment. The extended-delta starter combines the benefits of reduced voltage starting with an efficient transition to full voltage running conditions, ensuring smooth operation and protecting both the motor and the electrical infrastructure.

8.1.1 Principle of Extended-Delta Reduced-Voltage Starter Circuits

The principle behind the extended-delta reduced-voltage starter circuit is to initially apply a reduced voltage to the stator windings of the three-phase asynchronous motor by connecting the motor in a special extended-delta configuration. This configuration effectively reduces the voltage across each winding to approximately 58% of the line voltage, which reduces the starting current to about one-third of the full voltage starting current. The motor then accelerates under this reduced voltage until it reaches a predetermined speed, after which the circuit switches to full line voltage for normal operation.

This starting method is particularly advantageous in environments with unstable or limited power supply, such as remote agricultural cooperatives or small-scale manufacturing units in emerging urban areas. It helps avoid excessive voltage drops that could affect other connected loads. Unlike conventional star-delta starters, the extended-delta starter provides better starting torque at reduced voltage, making it suitable for applications requiring moderate starting torque without high current surges.

8.1.2 Method of Implementing Extended-Delta Reduced-Voltage Starter Circuits

Implementing an extended-delta starter involves a specific wiring arrangement and switching sequence of the motor windings and contactors. The motor is initially connected in an extended-delta configuration using three contactors and appropriate resistors or reactors to reduce the voltage applied to each phase. The control circuit ensures a smooth transition from reduced voltage starting to full voltage running by sequentially switching the contactors.

In a practical scenario such as a county government office with multiple HVAC units, this method enables the motors driving the compressors to start without causing significant disturbances in the local power network. The reduced starting current also extends the lifespan of the motor windings by limiting thermal and mechanical stresses during startup.

Name Specification Use
Main Contactor Rated for full line voltage and current Connects motor windings for full voltage operation
Extended-Delta Contactor Rated for reduced voltage operation Connects motor windings in extended-delta configuration
Timer Relay Adjustable timing control Controls the switching interval between reduced and full voltage
Overload Relay Current rating matching motor Protects motor from overcurrent
  • The starting sequence begins with energizing the extended-delta contactor, applying reduced voltage to the motor.
  • The timer relay counts down the preset starting time, allowing the motor to accelerate under reduced voltage.
  • Upon timer completion, the main contactor activates while the extended-delta contactor deactivates, applying full line voltage.
  • The overload relay continuously monitors motor current to prevent damage from excessive load or faults.
  • Proper coordination among these components ensures smooth operation and protects both the motor and supply system.

8.1.3 Advantages of Extended-Delta Reduced-Voltage Starter Circuits

Extended-delta reduced-voltage starters offer several benefits important to Kenyan industries operating with constrained power infrastructure or sensitive electrical loads. They reduce mechanical stress and electrical disturbances during motor startup, improving system reliability and reducing maintenance costs.

Advantages

  • Reduced Starting Current: Limits inrush current to approximately one-third of direct-on-line starting current, minimizing voltage dips in the supply network.
  • Improved Starting Torque: Provides higher starting torque than star-delta starters at reduced voltage, suitable for loads requiring moderate torque such as water pumps in agricultural irrigation schemes.
  • Enhanced Motor Protection: Limits thermal and mechanical stresses on the motor windings, extending motor lifespan and reducing downtime in facilities like county hospitals.
  • Smooth Transition to Full Voltage: The controlled switching sequence prevents sudden torque changes, reducing mechanical wear on connected equipment.
  • Energy Efficiency: By reducing the initial current surge, the starter helps avoid unnecessary energy losses, contributing to operational cost savings in commercial buildings such as hotels and retail outlets.

8.1.4 Limitations and Considerations in Using Extended-Delta Starters

While the extended-delta reduced-voltage starter offers several advantages, it also has limitations and requires careful consideration during selection and installation. Understanding these factors is essential to ensure optimal performance and avoid equipment damage or operational issues.

Limitations

  • Complex Control Wiring: The starter circuit involves multiple contactors and timing relays, increasing installation complexity compared to simpler starters.
  • Cost: Components such as timer relays and additional contactors add to the initial cost, which may be significant for small enterprises like local SACCOs or small-scale farms.
  • Limited Starting Torque Range: While improved over star-delta starters, the torque available at reduced voltage may still be insufficient for very heavy loads, necessitating alternative starting methods.
  • Maintenance Requirements: More components increase the likelihood of faults and require regular inspection and maintenance to ensure reliability.
  • Space Constraints: The extended-delta starter requires more panel space than direct-on-line or star-delta starters, which may be a challenge in compact installations such as small retail shops or mobile clinics.

Considering these factors, organizations such as universities with multiple motor-driven systems must weigh the benefits against the costs and complexity when choosing motor starting methods.

Practice Questions

  1. Explain the principle of the extended-delta reduced-voltage starter circuit and how it reduces starting current in a three-phase asynchronous motor. (10 marks)
  2. Describe the method of implementing an extended-delta starter circuit, including the role of the main components involved. (12 marks)
  3. Discuss five advantages of using extended-delta reduced-voltage starters in industrial motor applications. (10 marks)
  4. Identify and explain five limitations or considerations when using extended-delta reduced-voltage starters. (10 marks)
The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒8.2 Connection and debugging methods of extended-delta reduced-voltage starter circuits of three-phase asynchronous motor

The extended-delta reduced-voltage starter circuit is a sophisticated method used to start three-phase asynchronous motors with lower starting current and reduced mechanical stress. This technique is common in Kenyan industries where large motors operate criti…

🔒8.3 Diagnosis of extended-delta reduced-voltage starter circuits of three-phase asynchronous motor

In Kenyan industries ranging from county referral hospitals to agricultural cooperatives, three-phase asynchronous motors are widely used to drive pumps, compressors, and conveyors. Employing extended-delta reduced-voltage starter circuits is a common method t…

🔒8.4 Writing diagnosis reports

In professional settings across Kenya, from county referral hospitals to universities and retail businesses, clear and accurate diagnosis reports are essential for effective decision-making and problem resolution. In electrical motor control, particularly when…

Chapter Summary

This chapter explored the principle and method behind extended-delta reduced-voltage starter circuits used for three-phase asynchronous motors, explaining how this approach effectively limits starting current and reduces electrical stress. It detailed the correct procedures for connecting and debugging these starter circuits, emphasizing the importance of proper wiring and testing to ensure optimal motor performance and safety. The chapter also covered techniques for diagnosing faults within the extended-delta starter circuits, enabling technicians to identify common issues such as wiring errors, component failures, or improper operation. Finally, it addressed the proper way to document diagnosis findings through clear and structured reports, ensuring that maintenance records are comprehensive and useful for future reference. This comprehensive treatment ensures a thorough understanding of both the theoretical and practical aspects of extended-delta reduced-voltage starters in motor control.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. What is the primary purpose of using an extended-delta reduced-voltage starter circuit in a three-phase asynchronous motor? (3 marks)
  2. Describe the method of connecting an extended-delta reduced-voltage starter circuit. (4 marks)
🔒20 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Explain the principle of the extended-delta reduced-voltage starter circuit used in three-phase asynchronous motors, citing an example from a county hospital where such a starter might enhance motor longevity. (4 marks)
  2. Identify and describe the main components involved in the connection of an extended-delta reduced-voltage starter circuit for a three-phase asynchronous motor. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Explain and Demonstrate the Principle of Extended-Delta Reduced-Voltage Starter Circuit

Refrigeration And Air Conditioning · Level 5
Electrical Motor Control Principles
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Explain verbally and demonstrate the working principle of an extended-delta reduced-voltage starter circuit for a three-phase asynchronous motor using a model circuit board (rated 3 kW, 415 V).
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Insulated Screwdriver SetModel Extended-Delta Reduced-Voltage Starter Circuit Board
Digital MultimeterElectrical Connection Wires (1.5 mm²)
Extended-Delta Starter Circuit Schematic Diagram
Service Manual for Extended-Delta Starters
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Model Extended-Delta Reduced-Voltage Starter Circuit Board1 Pc Per Candidate
2Insulated Screwdriver Set1 Set Per Candidate
3Digital Multimeter1 Pc Per Candidate
4Electrical Connection Wires (1.5 mm²)5 Meters Per Candidate
5Safety Gloves1 Pair Per Candidate
6Safety Boots1 Pair Per Candidate
7Protective Goggles1 Pair Per Candidate
8Extended-Delta Starter Circuit Schematic Diagram1 Pc Per Candidate
9Service Manual for Extended-Delta Starters1 Pc Per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Safety and Preparation
Wore appropriate PPE: safety gloves, boots, and goggles
(Award 1 mark for all PPE worn correctly)
1
Handled tools and equipment safely as per workshop procedures
(Award 1 mark for correct handling and safety)
1
Checked the specifications of the model motor and starter circuit (3 kW, 415 V)
(Award 1 mark for correctly identifying specifications)
1
Interpreted the extended-delta starter circuit schematic diagram correctly
(Award 2 marks for correct interpretation of wiring and components)
2
Sub-Total5
TASK 2: Explanation and Demonstration
Explained the principle of the extended-delta reduced-voltage starter circuit clearly
(Award up to 5 marks for clear and accurate explanation including current path and voltage reduction method)
5
Demonstrated the operation by energizing the model starter circuit safely
(Award 3 marks for correct demonstration including switching sequence)
3
Measured and showed voltage reduction across the motor terminals using a multimeter
(Award 2 marks for correct measurement and interpretation)
2
Answered assessor’s questions related to the advantages and limitations of extended-delta starters
(Award 2 marks for satisfactory responses)
2
Sub-Total12
TASK 3: Housekeeping and Reporting
Performed housekeeping by cleaning the workstation and storing tools properly
(Award 1 mark for proper housekeeping)
1
Prepared a brief verbal or written report including title, tools used, procedure, and principle explained
(Award 2 marks for completeness and clarity of report)
2
Sub-Total3
PRODUCT CHECKLIST
Accuracy of demonstration: correct wiring setup and correct voltage readings (3 kW, 415 V, reduced voltage at start)
(Award 5 marks for correct and functional demonstration setup)
5
Clarity and completeness of verbal explanation and report
(Award 3 marks for clear, logical, and complete explanation and report)
3
Sub-Total8
GRAND TOTAL28
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Debug extended-delta reduced-voltage starter circuit faults

Refrigeration And Air Conditioning · Level 5
Electrical Motor Control Principles
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Diagnose and correct wiring and connection faults in an extended-delta reduced-voltage starter circuit for a 5 HP three-phase asynchronous motor.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Digital MultimeterElectrical Tape
Clamp MeterSafety Gloves
Insulated Screwdriver SetSafety Boots
PliersDust Coat/Overall
Wire Strippers and CuttersSafety Goggles
Allen Keys Set
Tweezers
Insulation Tester
Soldering Iron
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Extended-delta starter circuit panel (pre-wired with faults)1 Pc per Candidate
2Three-phase asynchronous motor (5 HP, 415 V)1 Pc per Candidate
3Digital Multimeter1 Pc per Candidate
4Clamp Meter1 Pc per Candidate
5Insulated Screwdriver Set1 Set per Candidate
6Pliers1 Pc per Candidate
7Wire Strippers and Cutters1 Pc per Candidate
8Allen Keys Set1 Set per Candidate
9Electrical Tape1 Roll per Candidate
10Tweezers1 Pc per Candidate
11Insulation Tester (Megger)1 Pc per Candidate
12Service Manual for Extended-Delta Starter Circuits1 Pc per Candidate
13Soldering Iron with Solder1 Pc per Candidate
14Safety Gloves1 Pair per Candidate
15Safety Boots1 Pair per Candidate
16Dust Coat/Overall1 Pc per Candidate
17Safety Goggles1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Preparation and Safety Compliance
Wore all required PPE: dust coat/overall, safety boots, gloves, goggles
(Award 1 mark for correct PPE usage)
1
Handled tools and equipment according to workshop safety procedures
(Award 1 mark for correct tool handling and safety observance)
1
Sub-Total2
TASK 2: Fault Diagnosis
Inspected and identified wiring faults in the extended-delta starter circuit
(Award 1 mark for accurate fault identification)
1
Checked electrical connections for loose or incorrect wiring
(Award 1 mark for thorough connection inspection)
1
Tested motor windings continuity using a multimeter
(Award 1 mark for correct continuity testing)
1
Checked insulation resistance of motor and starter wiring using insulation tester
(Award 1 mark for proper insulation testing)
1
Verified starter coil and contactor operation
(Award 1 mark for correct starter component testing)
1
Sub-Total5
TASK 3: Fault Correction and Repair
Corrected wiring faults by reconnecting or replacing faulty wires as per circuit diagram
(Award 2 marks for proper correction and neat wiring)
2
Replaced or refurbished worn or damaged parts in the starter circuit
(Award 1 mark for component replacement or refurbishment)
1
Used soldering iron to secure connections where necessary
(Award 1 mark for neat and secure soldered joints)
1
Applied electrical tape correctly to insulate repaired connections
(Award 1 mark for proper insulation of connections)
1
Sub-Total5
TASK 4: Final Testing and Commissioning
Performed run test of the motor starter circuit
(Award 1 mark for successful run test)
1
Checked voltage and current readings are within specification during motor start
(Award 1 mark for correct electrical parameter verification)
1
Maintained motor protection systems and verified their operation
(Award 2 marks for correct motor protection maintenance and testing)
2
Sub-Total4
TASK 5: Housekeeping and Reporting
Cleaned work area and tools after completing the task
(Award 1 mark for good housekeeping)
1
Prepared a clear service report including title, tools used, fault identified, and corrective procedure
(Award 1 mark for complete and clear report)
1
Sub-Total2
PRODUCT CHECKLIST
Extended-delta starter circuit wiring corrected and connected as per the circuit diagram
(Award 3 marks for correct wiring and connections matching the diagram)
3
Motor starter components correctly installed and secure
(Award 2 marks for correct installation and secure fixing)
2
Electrical insulation and safety maintained on all wiring and connections
(Award 2 marks for proper insulation and safety)
2
Motor runs smoothly on start with correct voltage and current readings
(Award 2 marks for satisfactory motor operation and electrical parameters)
2
Sub-Total9
GRAND TOTAL27
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Perform Operational Test on Extended-Delta Reduced-Voltage Starter CircuitPractical 3
🔒Diagnose Electrical Faults in Extended-Delta Starter Circuit of a 3-Phase Asynchronous MotorPractical 4
🔒Diagnose Mechanical Faults Affecting Extended-Delta Starter Operation of a 3-Phase Asynchronous MotorPractical 5
🔒Prepare detailed diagnosis report for extended-delta reduced-voltage starter circuitPractical 6
🔒Interpret and Use Wiring Diagrams for Extended-Delta Reduced-Voltage StarterPractical 7
🔒Demonstrate Safety Procedures During Extended-Delta Reduced-Voltage Starter Circuit WorkPractical 8
Flashcards 20 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

18 more in this section.

Create a free account
Test Yourself 18 questions Start quiz ▾
0%
0 / 2
🔒

16 more in this section.

Create a free account
Am I competent?

At the start of this chapter we promised you would be able to:

  • Apply the principles and methods of extended-delta reduced-voltage starter circuits for delta reduced three-phase asynchronous motors based on job voltage starter requirements.
  • Correctly connect extended-delta reduced-voltage starter circuits for three-phase asynchronous motors following ASHRAE and IEE standards.
  • Debug extended-delta reduced-voltage starter circuits accurately to ensure proper motor operation.
  • Diagnose issues in extended-delta reduced-voltage starter circuits according to job requirements with confidence.
  • Prepare detailed and clear diagnosis reports following workplace procedures.

Tick each one you can genuinely do.

So, are you there yet?

You're competent when you can confidently do 50% or more of what this chapter promised.

Sign in to record how you're doing.