Plumbing  ·  Level 5
Fire Control Systems
Chapter 5: Install wet and dry risers
📚 9 Topics
⚑ What you will be able to do

By the end of this chapter, you will be able to:

  • Follow safety and health practices correctly according to work procedures to keep yourself and others safe.
  • Identify different types of wet and dry riser systems accurately based on standards and job requirements.
  • Install wet and dry riser fire suppression systems correctly, meeting all relevant standards and job requirements.

Mastering these skills ensures you can confidently contribute to effective fire safety solutions that protect lives and property in real-world situations.

Compiled by: Elijah Kiprono

Fire control systems are critical components in building safety, designed to protect lives and property by controlling or extinguishing fires. For plumbing professionals in Kenya, understanding the installation of wet and dry risers is essential, as these systems integrate closely with water supply infrastructure. Wet and dry risers provide reliable access to water for firefighting on multiple floors, especially in high-rise buildings, hospitals, hotels, and commercial complexes. Mastery of these systems ensures compliance with safety regulations and enhances emergency preparedness in various institutional and commercial settings.

5.1 Terms and concepts

Understanding the key terms and concepts related to wet and dry risers equips plumbing professionals with the technical language and foundational knowledge necessary for effective installation and maintenance. These terms clarify the components, functions, and operational principles of fire control systems, enabling precise communication with fire safety engineers, contractors, and regulatory bodies such as the National Construction Authority (NCA) and the Kenya Fire Brigade.

5.1.1 Wet Riser: Definition and Function

A wet riser is a vertical water pipe permanently charged with water, installed in multi-storey buildings to provide immediate water supply for firefighting. This system is connected to the building's main water supply and includes outlets on each floor where fire hoses can be attached.

Definition

  • A wet riser is a fixed pipe system filled with water at all times, ensuring readiness for immediate firefighting.
  • It is typically installed in buildings above 18 meters or six floors, as per Kenyan building codes.
  • The system includes inlet points at ground level for fire brigade water supply connection and outlets at each floor.
  • Wet risers maintain a pressurized water supply, eliminating delays in firefighting response.
  • The piping material is usually galvanized steel or ductile iron, resistant to corrosion and high pressure.

Function

  • Provides a direct water source for firefighting on upper floors.
  • Reduces reliance on external water sources, which may be inaccessible during emergencies.
  • Enables firefighters to quickly connect hoses and begin suppression.
  • Supports continuous water flow, critical for controlling fires in tall buildings.
  • Enhances occupant safety by reducing fire spread and enabling evacuation.

5.1.2 Dry Riser: Definition and Operational Principles

A dry riser is a vertical pipe system installed in buildings, which remains empty of water until connected to an external water source during a fire emergency. It allows firefighters to pump water into the system from the ground level.

Definition

  • Dry risers are empty pipes capped to prevent debris ingress.
  • Installed in buildings where water supply pressure is insufficient or where wet risers are impractical.
  • Equipped with inlet valves at ground level and outlets on each floor.
  • Designed to be connected to fire engines or hydrants to deliver water upwards.
  • Constructed from steel or other durable materials to withstand high water pressure when charged.

Operational Principles

  • Water is introduced into the system by a fire engine or external pump.
  • Firefighters connect hoses to outlets at the fire floor, using supplied water.
  • The system requires regular maintenance to ensure airtight seals and valve functionality.
  • Dry risers are vital in locations without permanent pressurized water supply.
  • They provide flexibility for firefighting in older buildings or those with limited water infrastructure.

5.1.3 Components of Wet and Dry Risers

Both wet and dry risers consist of several critical components that ensure their functionality and compliance with safety standards. Understanding these components is vital for correct installation and troubleshooting.

Two types of wet riser systems used in fire protection
Two types of wet riser systems used in fire protection (Source: PLUMB 5 LEARNING GUIDE-1 (1))

Components

  • Inlet Valve: Allows connection of water supply at ground level; must be accessible and clearly marked.

  • Outlet Valve/Branch Pipe: Located on each floor for hose connection; fitted with control valves to regulate water flow.

  • Riser Pipe: The vertical pipe that transports water between floors; sized according to building height and water demand.

  • Landing Valves: Positioned at outlet points; designed for quick hose attachment and shut-off.
  • Pressure Relief Valves (wet risers only): Prevent excessive pressure buildup, protecting the system and pipework from damage.

5.1.4 Regulatory Standards and Codes Relevant to Installation

Compliance with Kenyan and international fire safety standards ensures that wet and dry risers are installed to provide maximum safety and operational reliability. Plumbing professionals must be familiar with these regulations.

Relevant Standards

  • Kenya Building Code: Specifies requirements for fire control systems, including riser installation height, material specifications, and maintenance.
  • Kenya Bureau of Standards (KEBS): Provides guidelines on materials and workmanship for plumbing and fire safety systems.
  • National Construction Authority (NCA) Regulations: Enforces standards for building safety, including fire risers.
  • Fire Safety and Prevention Act: Mandates proper fire safety measures in public and commercial buildings.
  • International Standards (e.g., BS 9990): Often referenced in Kenya for design and installation best practices.
The rest of this chapter
🔒

Create a free account to open more of this chapter.

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒5.2 Safety and health practices

Safety and health practices are paramount during the installation of wet and dry risers to protect workers and occupants. Plumbing professionals must observe strict protocols to prevent accidents, comply with occupational health regulations, and ensure the int…

🔒5.3 Types of riser's systems

In the field of plumbing, understanding the various types of riser systems is critical for the effective design and installation of fire control infrastructure in buildings. In Kenya, where urban development includes multi-storey residential, commercial, and p…

🔒5.4 Installation of fire suppression systems

Fire suppression systems are vital components in building safety, designed to control or extinguish fires in their early stages. For plumbers in Kenya, the installation of these systems requires adherence to stringent standards to ensure reliability and effect…

🔒5.5 Functionality tests

Functionality testing of wet and dry risers is a critical stage after installation in plumbing systems, ensuring that fire control infrastructure performs reliably under emergency conditions. In Kenya, where many multi-storey buildings in Nairobi, Mombasa, and…

🔒5.6 Faults in fire risers' systems

Fire risers are vital life safety components, but they are prone to faults that may compromise their effectiveness during emergencies. In Kenya’s diverse climatic and operational environments, plumbing professionals must understand common faults, their causes,…

🔒5.7 Correcting faults

Correcting faults in wet and dry risers is a critical task that ensures the reliability and safety of fire control systems within buildings and other infrastructure. For plumbing professionals in Kenya, especially those working in commercial buildings, hospita…

🔒5.8 Commissioning

Commissioning wet and dry risers is the final and crucial phase in the installation process that ensures the system meets design specifications and is ready for operational use. For plumbing professionals in Kenya, commissioning confirms compliance with nation…

🔒5.9 House Keeping

In plumbing projects involving the installation of wet and dry risers, good housekeeping is vital for maintaining a safe, efficient, and professional work environment. In Kenya, construction and plumbing sites often face challenges such as limited space, high…

Chapter Summary

This chapter introduced key terms and concepts essential for understanding fire control systems, particularly focusing on wet and dry risers. It emphasized the importance of adhering to safety and health practices during installation and maintenance to protect workers and ensure system reliability. Various types of riser systems were examined, highlighting their distinct features and applications. The installation procedures for dry pipe and wet pipe systems were discussed in detail, outlining the technical steps required for effective fire suppression. Functionality tests were explained as critical measures to verify the operability of the installed systems. Common faults in fire risers were identified, along with practical methods for diagnosing and correcting these issues to maintain performance. The chapter also covered the commissioning process, ensuring that systems meet regulatory standards before being put into service. Finally, the significance of proper housekeeping was underscored to preserve system integrity and readiness for emergencies.

Self-Assessment

🔒 PDFDownload this self-assessment, with answers

A. Written Assessment

  1. Define the term "wet riser" and explain its primary use in fire control systems. (4 marks)
  2. What are the main safety precautions a plumber must observe when installing dry riser systems? (5 marks)
🔒20 more in this section.

Chapter Examination Questions

🔒 PDFDownload these examination questions, with worked answers

SECTION A (40 Marks) - Answer ALL Questions

  1. Define the term "wet riser" and explain its primary function in a multi-storey building such as a Nairobi hotel. (4 marks)
  2. List four essential safety practices a plumber must observe when installing a dry riser system in a commercial building. (4 marks)
🔒18 more in this section.

Chapter Practical Activities

Practical 1: Identify and explain fire riser terminology

Plumbing · Level 5
Fire Control Systems
PRACTICAL ASSESSMENT
TIME: 3 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Identify and explain 10 key fire riser terminology terms related to wet and dry riser systems in a written report.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
PenFire riser terminology reference sheet
Notebook
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Fire riser terminology reference sheet1 Pc per Candidate
2Pen1 Pc per Candidate
3Notebook1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Use of personal protective equipment
Candidate uses gloves
(Award 1 mark if gloves worn, else zero)
1
Candidate wears overall
(Award 1 mark if overall worn, else zero)
1
Candidate wears industrial boots
(Award 1 mark if boots worn, else zero)
1
Sub-Total3
TASK 2: Identification of fire riser terminology
Candidate identifies at least 10 key fire riser terms such as inlet valve, outlet valve, landing valve, dry riser, wet riser, pressure gauge, test valve, non-return valve, fire brigade landing valve, and siamese connection
(Award 0.5 marks for each correctly identified term, total 5 marks)
5
Candidate explains the function of each identified term correctly
(Award 0.5 marks for each correct explanation, total 5 marks)
5
Sub-Total10
PRODUCT CHECKLIST
Written report contains clear, correct definitions and explanations of all 10 fire riser terms
(Award 0.7 marks for each accurate and well-explained term, total 7 marks)
7
Report is legible, well-organized, and free from spelling or grammatical errors
(Award 3 marks for neat, organized, error-free report, else zero)
3
Sub-Total10
GRAND TOTAL23
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Implement safety and health measures during installation of wet and dry risers

Plumbing · Level 5
Fire Control Systems
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Demonstrate correct safety and health practices during installation of wet and dry risers using 19mm GI pipes and associated fittings.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
Pipe wrenchGI Pipe
Pipe cutterGate valve
Pipe threading equipmentGI Tee
HacksawGI Elbow
Die stockFire sprinkler
Vice - BenchWater tank
Ball hammerG.I Back nut
Wall clipsG.I Long nipple
Fire pump (pump booster)
Teflon tape
Non-return valve
Nipple
Union
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1Personal Protective Equipment (PPE): gloves, overall, industrial boots1 full set per Candidate
219mm diameter GI Pipe2 meters per Candidate
319mm diameter gate valve1 Pc per Candidate
419mm diameter GI Tee1 Pc per Candidate
519mm diameter GI Elbow4 Pcs per Candidate
6Fire sprinkler2 Pcs per Candidate
7Water tank1 Pc per Candidate
819mm diameter G.I Back nut2 Pcs per Candidate
919mm diameter G.I Long nipple1 Pc per Candidate
10Fire pump (pump booster)1 set per Candidate
11Teflon tapeSufficient per Candidate
12Connect non-return valve1 Pc per Candidate
13Connect nipple2 Pcs per Candidate
14Connect union2 Pcs per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Implement safety and health practices
Used personal protective equipment correctly: gloves, overall, industrial boots
(Award 1 mark for each PPE worn or zero = 3 marks)
3
Identified and assembled correct tools and equipment for the installation
(Award 1 mark each for at least 3 tools correctly identified and assembled or zero = 3 marks)
3
Handled pipes and fittings carefully to avoid damage and injury
(Award 2 marks or zero)
2
Followed safe cutting and threading procedures
(Award 2 marks or zero)
2
Used tools and equipment correctly and safely during installation
(Award 1 mark each for correct use of pipe wrench, cutter, threading equipment or zero = 3 marks)
3
Ensured proper waste disposal of pipe offcuts and debris
(Award 2 marks or zero)
2
Sub-Total15
PRODUCT CHECKLIST
Pipes and fittings handled without damage or injury risk
(Award 3 marks or zero)
3
Work area kept clean and organized with proper waste disposal
(Award 3 marks or zero)
3
Demonstrated awareness of occupational safety and health regulations during installation
(Award 4 marks or zero)
4
Sub-Total10
GRAND TOTAL25
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Differentiate Wet and Dry Riser Systems ComponentsPractical 3
🔒Installation of a Wet Pipe Fire Suppression System 6000mm x 4000mm LayoutPractical 4
🔒Installation of a Dry Pipe Fire Suppression SystemPractical 5
🔒Conduct functionality tests on wet riser systemPractical 6
🔒Conduct functionality tests on a dry riser systemPractical 7
🔒Identify and Diagnose Faults in Fire Riser SystemsPractical 8
🔒Correct faults in wet and dry fire riser systems restoring operational conditionPractical 9
🔒Commission an Installed Wet and Dry Riser Fire SystemPractical 10
🔒Perform housekeeping after installation of wet and dry fire risersPractical 11
Flashcards 20 cards Study deck ▾
Question
1

↻ Tap card to reveal answer
🔒

18 more in this section.

Create a free account
Test Yourself 17 questions Start quiz ▾
0%
0 / 2
🔒

15 more in this section.

Create a free account
Am I competent?

At the start of this chapter we promised you would be able to:

  • Follow safety and health practices correctly according to work procedures to keep yourself and others safe.
  • Identify different types of wet and dry riser systems accurately based on standards and job requirements.
  • Install wet and dry riser fire suppression systems correctly, meeting all relevant standards and job requirements.

Tick each one you can genuinely do.

So, are you there yet?

You're competent when you can confidently do 50% or more of what this chapter promised.

Sign in to record how you're doing.