Chapter 6: Test and commission mechatronic system
📚 0 Topics

Chapter Practical Activities

Practical 1: Functional Testing of Mechatronic Components

Mechatronics Technology · Level 5
Mechatronic System Installation
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Perform functional testing of a mechatronic system consisting of a proximity sensor, double-acting pneumatic cylinder 100mm bore x 200mm stroke, 5/2 solenoid valve (24VDC), LED lamp (24VDC), and mode selector switch (2-position).
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
PLC (minimum 6 I/Os)Proximity sensor, 24VDC (NPN or PNP)
24V DC power supplyDouble-acting pneumatic cylinder
240V AC power supply5/2 solenoid valve (24VDC)
MultimeterAir compressor with FRL unit
PLC programming cable and PCLED lamp (24VDC)
ScrewdriversMode selector switch (2-position)
Wire stripperPush button (NO)
PliersCircuit breaker (6A-10A)
Electrical wires
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1PLC (minimum 6 I/Os)1 Pc Per Candidate
224V DC power supply1 Pc Per Candidate
3240V AC power supply1 Pc Per Candidate
4Proximity sensor, 24VDC (NPN or PNP)1 Pc Per Candidate
5Double-acting pneumatic cylinder1 Pc Per Candidate
65/2 solenoid valve (24VDC)1 Pc Per Candidate
7Air compressor with FRL unit1 Pc Per Candidate
8LED lamp (24VDC)1 Pc Per Candidate
9Mode selector switch (2-position)1 Pc Per Candidate
10Push button (Normally Open)2 Pcs Per Candidate
11Circuit breaker (6A-10A)1 Pc Per Candidate
12Electrical wiresAs required per Candidate
13PLC programming cable and PC1 Set Per Candidate
14Computer with PLC programming software installed1 Pc Per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Prepare and observe safety procedures
Candidate wears overall/dust coat
(Award 1 mark if worn, otherwise 0)
1
Candidate wears safety boots
(Award 1 mark if worn, otherwise 0)
1
Sub-Total2
TASK 2: Identify mechatronic components correctly
Identifies proximity sensor correctly
(Award 1 mark for correct identification)
1
Identifies double-acting pneumatic cylinder correctly
(Award 1 mark for correct identification)
1
Identifies 5/2 solenoid valve (24VDC) correctly
(Award 1 mark for correct identification)
1
Identifies LED lamp (24VDC) correctly
(Award 1 mark for correct identification)
1
Identifies mode selector switch (2-position) correctly
(Award 1 mark for correct identification)
1
Identifies push button (NO) correctly
(Award 1 mark for correct identification)
1
Identifies circuit breaker (6A-10A) correctly
(Award 1 mark for correct identification)
1
Sub-Total7
TASK 3: Connect and power the system safely
Installs and wires the circuit breaker correctly
(Award 2 marks if wired correctly and power supplied safely)
2
Connects and wires the mode selector switch (manual/auto) correctly
(Award 3 marks for correct mounting and wiring)
3
Connects and wires all inputs: sensor, push buttons, selector switch
(Award 2 marks for each correct connection)
6
Connects and wires all outputs: solenoid valve and LED lamp
(Award 2 marks for each correct connection)
4
Follows installation SOP: power off during connections, closes FRL valve when required, adheres to color codes, maintains tidy workspace
(Award 1 mark for each correct procedure followed)
4
Sub-Total19
TASK 4: Test pneumatic system and develop I/O mapping
Connects and tests pneumatic system with double-acting cylinder
(Award 3 marks for correct pneumatic connection and operation)
3
Develops accurate I/O mapping table
(Award 4 marks for complete and correct mapping)
4
Sub-Total7
TASK 5: Program and test PLC logic
Programs PLC with correct automatic mode logic (sensor triggers actuator and LED with 1-minute timer)
(Award 5 marks for correct programming)
5
Programs PLC with correct manual mode logic (push buttons control actuator and LED)
(Award 5 marks for correct programming)
5
Tests both manual and automatic modes successfully
(Award 4 marks if mode switching and operations work correctly)
4
Sub-Total14
TASK 6: Operate and disassemble the system safely
Operates the system: sensor activates cylinder reciprocation and LED turns ON
(Award 4 marks for correct operation sequence)
4
LED turns OFF after 1 minute as per timer
(Award 4 marks if LED turns OFF after 1 minute)
4
Switches OFF system and safely disassembles all components
(Award 3 marks for correct procedural action)
3
Returns all accessories and equipment to storage
(Award 1 mark if all equipment returned)
1
Sub-Total12
PRODUCT CHECKLIST
Functional testing confirms all components operate per specification: cylinder stroke 200mm, solenoid valve switching, sensor detection, LED illumination, and mode selector switching
(Award up to 10 marks for correct and verified component function and system operation matching task instruction)
10
Sub-Total10
GRAND TOTAL71
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)

Practical 2: Calibration of Sensors and Actuators in a Mechatronic System

Mechatronics Technology · Level 5
Mechatronic System Installation
PRACTICAL ASSESSMENT
TIME: 4 HOURS
⬇ PDFCandidate Instructions (Candidate Tool)

Type: Individual

INSTRUCTIONS TO CANDIDATE:
1.  You are required to perform the following task:
i.  Calibrate the proximity sensor and 5/2 solenoid valve actuator to achieve correct switching response and actuator stroke of 100mm.
2.  You have been provided with the following resources for the practical task:
Tools & EquipmentMaterials
MultimeterPLC (minimum 6 I/Os)
PLC programming cable and PC24V DC power supply
Proximity sensor, 24V DC (PNP)
5/2 solenoid valve (24V DC)
Double-acting pneumatic cylinder
LED lamp (24V DC)
Mode selector switch (2-position)
Push button (NO)
Circuit breaker (6A-10A)
Air compressor with FRL unit
Electrical wires
⬇ PDFResources Required (Cutting List)
S/NItemQuantity
1PLC (minimum 6 I/Os)1 Pc per Candidate
224V DC power supply1 Pc per Candidate
3Proximity sensor, 24V DC (PNP)1 Pc per Candidate
45/2 solenoid valve (24V DC)1 Pc per Candidate
5Double-acting pneumatic cylinder1 Pc per Candidate
6LED lamp (24V DC)1 Pc per Candidate
7Mode selector switch (2-position)1 Pc per Candidate
8Push button (NO)2 Pcs per Candidate
9Circuit breaker (6A-10A)1 Pc per Candidate
10Air compressor with FRL unit1 Pc per 3 Candidates
11Electrical wires5 m per Candidate
12Multimeter1 Pc per Candidate
13PLC programming cable and PC1 Pc per Candidate
14Computer with PLC programming software installed1 Pc per Candidate
⬇ PDFAssessor Guide
Items to be EvaluatedMarks AvailableMarks ObtainedComments
TASK 1: Observe Occupational Health and Safety
Wore overall/dust coat
(Award 2 marks if worn, otherwise 0)
2
Wore safety boots
(Award 2 marks if worn, otherwise 0)
2
Sub-Total4
TASK 2: Identify Components and Tools
Correctly identified proximity sensor
(Award 1 mark if correct)
1
Correctly identified 5/2 solenoid valve
(Award 1 mark if correct)
1
Correctly identified double-acting pneumatic cylinder
(Award 1 mark if correct)
1
Correctly identified mode selector switch
(Award 1 mark if correct)
1
Correctly identified LED lamp
(Award 1 mark if correct)
1
Correctly identified push buttons
(Award 1 mark if correct)
1
Correctly identified circuit breaker
(Award 1 mark if correct)
1
Correctly identified PLC and power supplies
(Award 1 mark if correct)
1
Sub-Total8
TASK 3: Connect and Power the System
Installed circuit breaker and supplied power safely
(Award 2 marks if correct installation and safety observed)
2
Connected and wired proximity sensor and push buttons correctly
(Award 2 marks for each correct input connection)
4
Connected and wired outputs (solenoid valve and LED lamp) correctly
(Award 2 marks for each correct output connection)
4
Adhered to wiring color codes and maintained tidy workspace
(Award 1 mark for each: color code adherence, tidy workspace, power off during wiring)
3
Sub-Total13
TASK 4: Calibrate Sensors and Actuators
Calibrated proximity sensor to detect target within 5 mm range
(Award 4 marks if sensor triggers reliably within 5 mm)
4
Calibrated solenoid valve to achieve actuator stroke of 100 mm
(Award 5 marks if actuator stroke is 100 ±2 mm)
5
Adjusted system timing to ensure actuator response within 1 second of sensor trigger
(Award 3 marks if timing is within 1 second)
3
Tested LED lamp to indicate actuator status correctly
(Award 2 marks if LED indicates ON/OFF status correctly)
2
Sub-Total14
TASK 5: Program and Test the PLC Logic
Programmed PLC for automatic mode: sensor triggers actuator and LED with 1-minute timer
(Award 5 marks if logic is correct and tested)
5
Programmed PLC for manual mode: push buttons control actuator and LED
(Award 5 marks if logic is correct and tested)
5
Tested manual and automatic modes successfully
(Award 4 marks if both modes operate correctly)
4
Operated system sequence: sensor activates actuator reciprocation and LED
(Award 4 marks if sequence operates correctly)
4
LED turns off after 1-minute timer expires
(Award 4 marks if LED turns off after 1 minute)
4
Sub-Total22
TASK 6: Shutdown and Housekeeping
Switched off power and closed FRL valve before disassembly
(Award 3 marks if done correctly)
3
Disassembled components using correct procedures
(Award 3 marks if correct procedures and tools used)
3
Returned all accessories and equipment to storage
(Award 1 mark if all returned properly)
1
Maintained clean and tidy workspace after completion
(Award 2 marks if workspace is clean and tidy)
2
Sub-Total9
PRODUCT CHECKLIST
Proximity sensor calibrated to detect target within 5 mm
(Award 4 marks if detection distance is within tolerance)
4
Actuator stroke adjusted to 100 ±2 mm
(Award 5 marks if stroke length is within tolerance)
5
PLC program implements correct auto and manual logic
(Award 6 marks if PLC logic matches requirements and tested)
6
System operates sequence correctly with LED indication and timing
(Award 5 marks if operation sequence is correct and LED timing accurate)
5
Sub-Total20
GRAND TOTAL90
ASSESSMENT OUTCOME:   ☐ Competent    ☐ Not Yet Competent (competent if at least 50%)
🔒

Free: practical guides, quick cards, workplace scenarios and more.

Create a free account
🔒Troubleshoot and rectify faults in a mechatronic systemPractical 3
🔒Perform Safety Checks and Compliance Verification on a Mechatronic SystemPractical 4
🔒Programming and parameter setting of a mechatronic control unitPractical 5
🔒Performance Validation of Mechatronic System Under Load ConditionsPractical 6
🔒Documentation of Test Results and Commissioning Report for a Mechatronic SystemPractical 7
🔒Wiring and Connection Verification of a Mechatronic SystemPractical 8
🔒Final Start-Up and Demonstration of Mechatronic SystemPractical 9